Owner's manual

EZ-ZONE PM Limit Express 18 Operations Menu
Operations Menu
Display Parameter Name Description
Range
Defaults are shown bold
[`LL;S]
[ LL.S]
Limit Low Set Point
Set the low process value that will trig-
ger the limit.
Appears if: Limit sides set to low or both.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 0.0°F or -18.0°C
[`Lh;S]
[ Lh.S]
Limit High Set Point
Set the high process value that will trig-
ger the limit.
Appears if: Limit sides set to high or both.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 0.0°F or -18.0°C
[`A;Lo]
[ A.Lo]
Alarm Low Set Point
Process - set the process value that will
trigger a low alarm.
Appears if: Alarm Type (A.ty) is set to
Process Alarm
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 32.0°F or 0.0°C
[`A;hi]
[ A.hi]
Alarm High Set Point
Process - set the process value that will
trigger a high alarm.
Appears if: Alarm Type (A.ty) is set to
Process Alarm
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 300.0°F or 150.0°C
[`i;CA]
[ i.CA]
Calibration Offset
Set an offset value for a process output.
Appears if: Always
-1,999.000 to 9,999.000°F or units
-1,110.555 to 5,555.000°C
0.0
[````] PAr1
[````] PAr2
[`ll;s] Limit Low Set Point
[`lh;s] Limit High Set Point
[`A;lo] Alarm Low Point
[`A;hi] Alarm High Point
[`i;Ca] Calibration Offset
Operations Menu
Upon power up of the control,
using the advance key will scroll
through the various prompts found
in the Operations Menu. At any
point within the Operations menu
to return to the default display push
the Reset key.