Instruction Manual
Watlow EZ-ZONE
®
PM Limit Controller • 29 • Chapter 2 Install and Wire
Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation be-
tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.
Note:
The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.
Activity Status
Indicator State Summary Requirement
Flashing Green Detectsactivity
IftheMACdetectsactivity,theLEDwillbe
flashing green.
Red - - - -
IftheMACdetectsacollision,theLEDwillbe
red.
DeviceNet™ Communications
CAN_L
V-
V+
CH
SH
CL
V-
T2
S2
R2
Slot B or E
V+
CAN_H
shield
Terminal Signal Function
V+ V+ DeviceNet™power
CH CAN_H positivesideofDevi-
ceNet™bus
SH shield shield interconnect
CL CAN_L negativesideofDevi-
ceNet™bus
V- V- DeviceNet™powerre-
turn
PM [4, 6, 8, 9] _ _ _ _ - [5] _ _ _ _ _ _
DeviceNet LED Indicators
ViewingthecontrolfromthefrontandthenlookingontoptwoLEDscanbe
seenalignedverticallyfronttoback.TheLEDclosesttothefrontisidentified
asthenetwork(Net)LEDwheretheonenexttoitwouldbeidentifiedasthe
module(Mod)LED.
Network Status
Indicator LED Description
Off
ThedeviceisnotonlineandhasnotcompletedtheduplicateMACIDtest
yet. The device may not be powered.
Green
The device is online and has connections in the established state (allcated
to a Master).
Red
Failed communication device. The device has detected an error that has
rendereditincapableofcommunicatingonthenetwork(duplicateMACID
or Bus-off).
Flashing Green
The device is online, but no connection has been allocated or an explicit
connection has timed out.
Flashing Red A poll connection has timed out.
Module Status
Indicator LED Description
Off No power is applied to the device.
Flashing Green-Red The device is performing a self-test.
Flashing Red Major Recoverable Fault.
Red Major Unrecoverable Fault.
Green The device is operating normally.