Instruction Manual

Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation be-
tween Analog Input 1, Digital I/O,
Switched dc/open collector outputs
and Process outputs to prevent
ground loops.
Note:
The control output common
terminal and the digital common
terminal are referenced to different
voltages and must remain isolated.
Watlow EZ-ZONE
®
PM Limit Controller 30 Chapter 2 Install and Wire
Profibus DP Communications
485 T-/R-
+5Vdc Voltage Potential
VP
B
A
DG
trB
B
A
trA
Slot B & E
485 T+/R+
Digital ground
Te rmination resistor B
485 T+/R+
485 T-/R-
Te rmination resistor A
• WireT-/R-totheA
terminal of the EIA-
485 port.
• WireT+/R+totheB
terminal of the EIA-
485 port.
• WireDigitalGround
to the common ter-
minal of the EIA-485
port.
• Donotroutenetwork
wires with power
wires. Connect net-
work wires in daisy-
chain fashion when
connecting multiple
devices in a network.
• Aterminationresistorshouldbeusedif
this control is the last one on the network.
•Ifusinga150ΩcableWatlowprovidesin-
ternal termination. Place a jumper across
pins trB and B and trA and A.
•If external termination is to be used with a
150Ωcableplacea390Ωre-sistoracross
pinsVPandB,a220Ωresistoracrosspins
BandA,andlastly,placea390Ωresistor
acrosspinsDGandA.
• Donotconnectmorethan32EZ-ZONE
PM
controllers on any given segment.
• MaximumEIA-485networklength:1,200
meters (4,000 feet)
•1/8thunitloadonEIA-485bus.
PM [4, 6, 8, 9] _ _ _ _-[6] AAA AAA
Profibus Terminal EIA/TIA-485 Name Watlow Terminal Label Function
VP (Voltage Potential) - - - - VP +5Vdc
B-Line B B T+/R+
A-Line A A T-/R-
DP-GND common DG common
Profibus DP LED Indicators
Viewing the unit from the front and then looking on top of the RUI/GTW two
bi-colorLEDscanbeseenwhereonlythefrontoneisused.Definitionfollows:
Closest to the Front
Indicator LED Description
Red Profibus network not detected
Red
Flashing
Indicates that the Profibus card is waiting for data ex-
change.
Green Dataexchangemode