Instruction Manual
Watlow EZ-ZONE
®
PM Limit Controller • 43 • Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter Name
Description
Range Default
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`ei;S]
[ Ei.S]
Digital Input (5 to 6)
Event Status
View this event input state.
[`off] Off (62)
[``on]On(63)
- - - - Instance 5
Map 1 Map 2
1408 1648
Offset to next
instance equals
+20
0x6E(110)
5 to 6
5
140 10005 uint
R
NoDis-
play
EZ-Key/s (1 to 2)
Event Status
View this event input state.
[`off] Off (62)
[``on]On(63)
- - - - Instance 1
Map 1 Map 2
1328 1568
Instance 2
Map 1 Map 2
1348 1588
0x6E(110)
3to4
5
140 10005 uint
R
[LiM]
[oPEr]
Limit Menu
[`LL;S]
[ LL.S]
Limit (1)
Limit Low Set Point
Set the low process value
that will trigger the limit.
-1,999.000to
9,999.000°Forunits
-1,128.000to
5,537.000°C
0.0°For
units
-18.0°C
Instance 1
Map 1 Map 2
684 724
0x70(112)
1
3
38 12003 float
RWES
[`Lh;S]
[ Lh.S]
Limit (1)
Limit High Set Point
Set the high process value
that will trigger the limit.
-1,999.000to
9,999.000°Forunits
-1,128.000to
5,537.000°C
0.0°For
units
-18.0°C
Instance 1
Map 1 Map 2
686 726
0x70(112)
1
4
39 12004 float
RWES
[`l;Cr]
[ L.Cr]
Limit (1)
Limit Clear Request
Clear limit once limit con-
dition is cleared.
[`Clr] Clear (0)
[ignr] Ignore (204)
0
Instance 1
Map 1 Map 2
680 720
0x70(112)
1
1
- - - - 12001 uint
W
[`l;st]
[ L.St]
Limit (1)
Limit State
Clear limit once limit con-
dition is cleared.
[`off] Off (62)
[none] None(61)
[`li;h] Limit High
(51)
[`li;l] Limit Low (52)
[`err] Error (28)
- - - -
Instance 1
Map 1 Map 2
690 730
0x70(112)
1
6
- - - - 12006 uint
R
[ALM]
[oPEr]
Alarm Menu
[`A;Lo]
[ A.Lo]
Alarm (1 to 4)
Alarm Low Set Point
If Alarm Type (Setup Page,
Alarm Menu) is set to:
process - set the process
value that will trigger a
low alarm.
-1,999.000to
9,999.000°Forunits
-1,128.000to
5,537.000°C
32.0°F
or
units
0.0°C
Instance 1
Map 1 Map 2
1482 1882
Offset to next
instance (Map
1) equals +50
Offset to next
instance (Map
2) equals +60
0x6D(109)
1to4
2
18 9002 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set










