Instruction Manual

Watlow EZ-ZONE
®
PM Limit Controller 53 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`lCr]
[ LCr]
Limit (1)
Limit Clear Request
*
Clear limit once limit
condition is cleared.
[`lCr] Clear (0)
[ignr] Ignore (204)
- - - -
Instance 1
Map 1 Map 2
680 720
0x70(112)
1
1
- - - - 12001 uint
W
[`l;st]
[ L.St]
Limit (1)
Limit Status *
Reflects whether or not
the limit is in a safe or
failed mode.
[fail]Fail(32)
[safe]Safe(1667)
- - - -
Instance 1
Map 1 Map 2
- - - - 744
0x70(112)
1
0x0D(13)
- - - - 12013 uint
R
NoDis-
play
Limit (1)
Limit State
Clear limit once limit
condition is cleared.
[`off] Off (62)
[none]None(61)
[`li;h]LimitHigh(51)
[`li;l] Limit Low (52)
[`err] Error (28)
- - - -
Instance 1
Map 1 Map 2
690 730
0x70(112)
1
6
- - - - 12006 uint
R
[otpt]
[`Set]
Output Menu
[``Fn]
[ Fn]
Output Digital (1 to 4)
Output Function
Select what function
will drive this output.
Note:
Output 2 is always a
limit. Use as primary
limit connection.
[`oFF] Off (62)
[LiM]Limit(126)
[ALM] Alarm (6)
Output1-
Alarm
Output 2 -
Limit
Output3-
Off
Output 4 -
Off
Instance 1
Map 1 Map 2
888 1008
Offset to next
instance (Map
1 & Map 2)
equals+30
0x6A(106)
1to4
5
83 6005 uint
RWES
[``Fi]
[ Fi]
Output Digital (1 to 4)
Output Function In-
stance
Set the instance of the
function selected above.
1to4 1 Instance 1
Map 1 Map 2
890 1010
Offset to next
instance (Map
1 & Map 2)
equals+30
0x6A(106)
1to4
6
84 6006 uint
RWES
[`o;ty]
[ o.ty]
Output Process (3)
Output Type
Select whether the pro-
cess output will operate
in volts or milliamps.
[uoLt]Volts(104)
[`MA]Milliamps(112)
Volts Instance 3
Map 1 Map 2
720 840
0x76(118)
3
1
95 18001 uint
RWES
[``Fn]
[ Fn]
Output Process (3)
Output Function
Set the type of func-
tion that will drive this
output.
[`oFF] Off (62)
[rmt]Retransmit(213)
[Ent;b]EventOutB(234)
[Ent;A]EventOutA(233)
[ALM] Alarm (6)
Off Instance 3
Map 1 Map 2
722 842
Instance 3
Map 1 Map 2
802 922
0x76(118)
3
2
96 18002 uint
RWES
[`r;Sr]
[ r.Sr]
Output Process (3)
Retransmit Source
Select the value that
will be retransmitted.
[``Ai]AnalogInput(142)
Analog
Input
Instance 3
Map 1 Map 2
804 924
0x76(118)
3
3
97 18003 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
* These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set