Instruction Manual

Watlow EZ-ZONE
®
PM Limit Controller 56 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[`A;Lo]
[ A.Lo]
Alarm (1 to 4)
Alarm Low Set Point
*
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the pro-
cess value that will
trigger a low alarm.
-1,999.000to9,999.000°For
units
-1,128.000to5,537.000°C
32.0°F
or units
0.0°C
Instance 1
Map 1 Map 2
1482 1882
Offset to next
instance (Map
1) equals +50
Offset to next
instance (Map
2) equals +60
0x6D
(109)
1to4
2
18 9002 float
RWES
[`A;hi]
[ A.hi]
Alarm (1 to 4)
Alarm High Set Point
*
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the pro-
cess value that will
trigger a high alarm.
-1,999.000to9,999.000°For
units
-1,128.000to5,537.000°C
300.0°F
or units
150.0°C
Instance 1
Map 1 Map 2
1480 1880
Offset to next
instance (Map
1) equals +50
Offset to next
instance (Map
2) equals +60
0x6D
(109)
1to4
1
19 9001 float
RWES
[`A;LA]
[ A.LA]
Alarm (1 to 4)
Alarm Latching
Turn alarm latching on
or off. A latched alarm
has to be turned off by
the user.
[nLAt] Non-Latching (60)
[`LAt] Latching (49)
Non-
Latching
Instance 1
Map 1 Map 2
1492 1892
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D(109)
1to4
7
27 9007 uint
RWES
[`A;bL]
[ A.bL]
Alarm (1 to 4)
Alarm Blocking
Select when an alarm
will be blocked. After
startup and/or after the
set point changes, the
alarm will be blocked
until the process
value enters the normal
range.
[`oFF] Off (62)
[`Str] Startup (88)
[StPt] Set Point (85)
[both]Both(13)
Off Instance 1
Map 1 Map 2
1494 1894
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D(109)
1to4
8
28 9008 uint
RWES
[`A;Si]
[ A.Si]
Alarm (1 to 4)
Alarm Silencing
Turn alarm silencing on
to allow the user to dis-
able this alarm.
[`oFF] Off (62)
[``on]On(63)
Off Instance 1
Map 1 Map 2
1490 1890
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D(109)
1to4
6
29 9006 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
* These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set