PM Limit Controller • 60 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[bAUd]
[bAUd]
Communications (1 or 2)
Baud Rate
Set the speed of this
controller'scommunica-
tions to match the speed
of the Modbus serial
network.
[9600]9,600(188)
[`19;2]19,200(189)
[`38;4] 38,400(190)
9,600 Instance 1
Map 1 Map 2
2484 2964
Instance 2
Map 1 Map 2
2504 2984
0x96(150)
1
3
- - - - 17002 uint
RWE
[`PAr]
[ PAr]
Communications (1 or 2)
Parity
Set the parity of this
controller to match the
parity of the Modbus se-
rial network.
[none] None
[EuEn] Even
[`odd] Odd
None Instance 1
Map 1 Map 2
2486 2966
Instance 2
Map 1 Map 2
2506 2986
0x96(150)
1
4
- - - - 17003 uint
RWE
[`C_f]
[ C_F]
Communications (1)
Display Units
Select whether this
communications chan-
nel will display in Cel-
sius or Fahrenheit.
Note:
Applies to Modbus
only.
[```f] Fahrenheit(30)
[```C]Celsius(15)
F Instance 1
Map 1 Map 2
2490 2970
0x96(150)
1
6
- - - - 17050 uint
RWE
[M;hL]
[M.hL]
Communications (1 or 2)
Modbus Word Order
Select the word order
ofthetwo16-bitwords
in the floating-point
values.
[Lohi] Low-High
[hiLo] High-Low
Low-High Instance 1
Map 1 Map 2
2488 2968
Instance 2
Map 1 Map 2
2508 2988
0x96(150)
1
5
- - - - 17043 uint
RWE
[Map]
[ Map]
Communications (1)
Data Map
Ifsetto1thecontrol
will use PM legacy map-
ping. If set to 2 the con-
trol will use new map-
ping to accommodate
new functions.
1to2 1if9
th
digit
of part
number
isa1
other-
wise, 2
- - - - - - - - - - - - 17059 uint
RWE
[`nU;S]
[ nV.S]
Communications (1)
Non-Volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM. The EEPROM
allows for approximate-
ly one million writes.
[`yes] Yes(106)
[``no] No (59)
Yes Instance 1
Map 1 Map 2
2494 2974
0x96(150)
1
8
198 17051 uint
RWE
[`Ad;d]
[ Ad.d]
Communications (2)
DeviceNet™ Node Ad-
dress
SettheDeviceNet™ad-
dress for this gateway.
0to63
63 - - - - - - - - - - - - 17052 - - - -
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
* These parameters/prompts are available in this menu with firmware revisions 11.0 and
above.
R: Read
W: Write
E: EEPROM
S: User Set