Instruction Manual

Watlow EZ-ZONE
®
PM Limit Controller 66 Chapter 7 Factory Page
Factory Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[Cust]
[fcty]
Custom Menu
[`par]
[ Par]
Custom
Parameter 1 to 20
Select the parameters
that will appear in the
Home Page.
TheParameter1value
will appear in the
upper display of the
Home Page. It cannot
be changed with the
UpandDownKeysin
the Home Page.
The Parameter 2 value
will appear in the low-
er display in the Home
Page. It can be changed
withtheUpandDown
Keys, if the parameter
is a writable one.
Scroll through the other
Home Page parameters
with the Advance Key
.
Note:
DisplayPairsaffect
the pairing of cus-
tom parameters on
the Home page. For
more information on
DisplayPairsseethe
section in this guide
entitled "Modifying
theDisplayPairs".
[nonE] None
[`l;st] Limit State
[`L;hy] Limit Hysteresis
[`Lh;S] Limit High Set
Point
[`LL;S] Limit Low Set
Point
[CUSt] Custom Menu
[`A;hy] Alarm Hysteresis
[`A;hi] Alarm High Set
Point
[`A;Lo] Alarm Low Set
Point
[USr;r] User Settings
Restore
[`C_F]DisplayUnits
[`i;CA] Calibration Offset
[`Pro] Process
See:
Home
Page
- - - - - - - - - - - - 14005 - - - -
[`iid]
[ iid]
Custom (1 to 20)
Instance ID
Select which instance of
the parameter will be
selected.
1to4 - - - - - - - - - - - - - - - - 14003 - - - -
[`LoC]
[FCty]
Lock Menu
[LoC;o]
[LoC.o]
Security Setting
Operations Page
Change the security
level of the Operations
Page.
1to3 2
Instance 1
Map 1 Map 2
18322302
0x67(103)
1
2
- - - - 3002
uint
RWE
[pas;e]
[LoC.P]
Security Setting
Password Enable
Set to On to require
a password for menu
changes.
[`off] Off
[``on] On
Off - - - - - - - - - - - -
3009
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set