Instruction Manual
Watlow EZ-ZONE
®
PM Limit Controller • 70 • Chapter 7 Factory Page
Factory Page
Dis-
play
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[ELi;o]
[ELi.o]
Calibration (1)
Electrical Input Offset
Change this value to
calibrate the low end of
the input range.
-1,999.000to9,999.000 0.0 Instance 1
Map 1 Map 2
378 378
0x68(104)
1
0xA(10)
- - - - 4010 float
RWES
[ELi;S]
[ELi.S]
Calibration (1)
Electrical Input Slope
Adjust this value to cali-
brate the slope of the
input value.
-1,999.000to9,999.000 1.0 Instance 1
Map 1 Map 2
380 380
0x68(104)
1
0xB(11)
- - - - 4011 float
RWES
[ELo;o]
[ELo.o]
Calibration (3)
Electrical Output
Offset
Change this value to
calibrate the low end of
the output range.
Menu 2 calibrates out-
put3.
-1,999.000to9,999.000 0.0 Instance 1
Map 1 Map 2
808 928
0x76(118)
3
5
- - - - 18005 float
RWES
[ELo;S]
[ELo.S]
Calibration (3)
Electrical Output
Slope
Adjust this value to cali-
brate the slope of the
output value.
Menu 2 calibrates out-
put3.
-1,999.000to9,999.000 1.0 Instance 1
Map 1 Map 2
730 850
0x76(118)
3
6
- - - - 18006 float
RWES
[``Pn]
[ Pn]
Calibration (1 to 2)
Part Number
Displayscurrentset-
ting for control model
number.
[fCty] Factory
[User] User
Factory - - - - - - - - - - - - - - - - uint
R
[Code]
[CodE]
Calibration (1 to 3)
Public Key
Changes the control to a
PM Express or back to
original model number
as shown on the side of
the control.
[2501] PM Express
[`606] Factory model
number
4999 - - - - - - - - - - - - - - - - uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be
read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set