Instruction Manual

PPC-2000 User’s Guide Chapter 5: LogicPro and Modbus Reference
Doc.# 30002-00 Rev 2.3 Watlow Anafaze 175
* 16-bit binary number
NOTE!
Refer to Setting up Control Channels on page 92 for
the basics of setting up closed-loop control channels.
Process Variable Source (PV Source)
This variable determines the input used as the process variable
for this channel. The process variable is a hardware input
converted to engineering units. A value of 0 indicates a channel
with no input. See Table 5.13 on page 176 through Table 5.17
on page 179 for a list and explanation of input numbering.
Cool Limit Time 49 0-32767 41401-41450 578-5A9
Sensor Fail Heat% 37 0-1000 41001-41050 3E8-419
Sensor Fail Cool% 52 0-1000 41551-41600 60E-63F
Heat Output Filter 31 0-100 40701-40750 2BC-2ED
Cool Output Filter 46 0-100 41251-41300 4E2-513
Heat Output% 36 0-1000 40951-41000 3B6-3E7
Cool Output% 51 0-1000 41501-41550 5DC-60D
Heat Output Destination 40 0-4102 41151-41200 47E-4AF
Cool Output Destination 55 0-4102 41701-41750 6A4-6D5
Alarm Parameters
Alarm Status Flags 82 * 45451-45500 154A-157B See
Table 5.28 on page 190
Alarm Control Flags 85 * 45601-45650 15E0-1611 See Table 5.30 on page 192
Alarm Acknowledge
Flags
88 * 45751-45800 1676-16A7 See Table 5.31 on page 192
Alarm Enable Flags 91 * 45901-45950 170C-173D See Table 5.32 on page 192
High Process Limit 80 45351-45400 14E6-1517
See explanation on p. 193
Low Process Limit 83 45501-45550 157C-15AD
High Deviation Offset 86 45651-45700 1612-1643
Low Deviation Offset 89 45801-45850 16A8-16D9
Alarm Deadband 92 0-255 45951-46000 173E-176F
Alarm Delay 93 0-100 46001-46050 1770-17A1
High Process Output
Destination
81
0-336
3103-4102
45401-45450 1518-1549
Low Process Output
Destination
84
0-336
3103-4102
45551-45600 15AE-15DF
High Deviation Output
Destination
87
0-336
3103-4102
45701-45750 1644-1675
Low Deviation Output
Destination
90
0-336
3103-4102
45851-45900 16DA-170B
Parameter # Range
Modbus
Address
Hex
Address
Notes