Instruction Manual

Chapter 5: LogicPro and Modbus Reference PPC-2000 User’s Guide
190 Watlow Anafaze Doc.# 30002-00 Rev 2.3
Table 5.27 Output Destinations for Soft
Boolean and Soft Integers
1
Soft Integers 1-100 may be used as output destinations.
Extended Soft Integers 101-2100 may not be used as output
destinations.
NOTE!
See Alarms on page 95 for an overview of alarm
functions.
Alarm Status Flags
Each Alarm Status register contains a 16-bit word. The bits may
be read to detect the status of each of a channel’s alarms. When
an alarm occurs, the controller sets the appropriate bit equal to
one. When the alarm condition clears, the controller sets the bit
back to 0. Table 5.28 summarizes these definitions. See Table
5.29 on page 191 for alarm bit definitions.
Table 5.28 Alarm Status
Value
AnaWin3 Name
(Soft Bool and Soft Int
1
Spreadsheets)
3001
3002
4000
PPC1:Soft Bool 1
PPC1:Soft Bool 2
PPC1:Soft Bool 1000
2051
2052
2150
PPC1:Soft Int 1
PPC1:Soft Int 2
PPC1:Soft Int 100
Value Condition
0 No alarm condition exists
1 Alarm condition exists