Instruction Manual

Chapter 5: LogicPro and Modbus Reference PPC-2000 User’s Guide
204 Watlow Anafaze Doc.# 30002-00 Rev 2.3
Table 5.43 Addresses for Analog Outputs on the
PPC-205x Analog Out Modules
1
The AnaWin3 names are shown for the first PPC-2000 in the system. See
Outputs on page
135
for a full explanation of analog output naming.
2
Use this address with the
Analog_Out_205x IO Driver
when addressing Analog Output Value.
There are no other analog output parameters so you will not use the
Database IO Driver
.
Analog Output Value
An array of addressable I/O words that represent the output
value for each analog output as a number between 0 and 32767.
These numbers correspond to the minimum and maximum
output signal levels for the selected Output Type. The analog
signal range is determined by the hardware, jumper
configuration, and the setting of the Output Type for the channel
with the output selected as Heat/Cool Output Destination.
Range: 0 to 32767
NOTE!
The resolution of the analog outputs is 12 bit. The
output Value is displayed as a 15-bit integer. The
output Value must change by more than seven to
effect a measurable change in an analog output.
AnaWin3 Name
1
(Output Spreadsheet)
LogicPro I/O Physical
Address
Modbus Addressing
Analog_Out_205x
IO Driver
2
Decimal Hex
PPC1:AO 31.1
PPC1:AO 31.2
PPC1:AO 31.8
31.1
31.2
31.8
46267
46268
46274
187A
187B
1881
PPC1:AO 32.1
PPC1:AO 32.2
PPC1:AO 32.8
32.1
32.2
32.8
46275
46276
46282
1882
1883
1889
PPC1:AO 33.1
PPC1:AO 33.2
PPC1:AO 33.8
33.1
33.2
33.8
46283
46284
46290
188A
188B
1891
PPC1:AO 34.1
PPC1:AO 34.2
PPC1:AO 34.8
34.1
34.2
34.8
46291
46292
46298
1892
1893
1899