Instruction Manual

Adaptive Addendum PPC-2000 User's Guide
0600-0049-0001 rev C Watlow Anafaze 1
PPC-2000 Adaptive Control
Addendum
Scope
This document describes the additional features and functionality found
in the PPC-2010-xxB with adaptive control. Refer to the PPC-2000
User’s Guide regarding all other functionality which is the same as the
standard version.
Introduction
The Watlow Anafaze PPC-2000 controller offers these standard options:
Forty-eight loops of conventional PID control with auto-tuning
capability
-or-
Eight loops of adaptive control plus 24 loops of conventional PID
control with auto-tuning for a total of 32 loops (the option described
in this document)
ANAWIN3 HMI software is available to support either option. A mix of
these options is not supported by ANAWIN3.
ANAWIN3 Software Installation
Follow the standard instructions to install and setup ANAWIN3. In the
setup program select the Adaptive Control option.
Spreadsheet Overview Screen
Several new parameters and options appear on the Spreadsheet Overview
screen in support of the adaptive control option. These parameters and
options are applicable only for the first eight channels and are omitted or
ignored for channels 9 to 32.
Control Type
An additional option appears for Control Type. Select Adaptive to enable
adaptive control and tuning on a channel. This option is only valid for
channels 1 to 8.
Values: PID1 (0), PID2 (1), Adaptive (2) and Retransmit (3)
Default: PID1 (0)
Modbus Address (Channels 1 to 32): 46401 to 46432
Parameter Number: 19
LogicPro Driver: Database
LogicPro Address (Channels 1 to 32): 19.1 to 19.32