Instruction Manual

PPC-2000 User’s Guide Chapter 1: Overview
Doc.# 30002-00 Rev 2.3 Watlow Anafaze 7
The PPC-2010 has 48 built-in digital I/O points. 24 points are
outputs only. 22 of these outputs are user configurable for PID
control, alarms or logic outputs. The other 2 outputs are
dedicated to system status and global alarm. The remaining 24
I/O points are individually configurable as either inputs or
outputs.
The following summarizes the processor’s features:
2 isolated communication ports
Transmit/receive indicators
Rotary switch for setting the Modbus network address
46 user configurable digital I/O
System status and digital output overload indicators
Real time clock
Flash PROM and battery backed RAM
Connects to terminal block board via 50-pin SCSI cable
PPC-2021 - 2022 Analog In Modules
The PPC-2021 and 2022 modules plug in to the module
expansion bus. The analog input modules support 16
differential inputs or 32 single-ended inputs, and accommodate
various sensors such as thermocouples (TCs), Resistive
Temperature Sensing Devices (RTDs) and linear transducers
using the terminal boards described later in this section.
Supports TCs, RTDs and linear voltage and current
signals
LED status indicator
DIN rail/panel mount
Connects to analog input terminal board via 50-pin SCSI
cable
PPC-2024 - 2025 Analog In High Isolation Modules
The PPC-2024 and 2025 modules plug in to the module
expansion bus. The high isolation analog input modules accept
8 or 16 differential analog inputs and accommodate various
sensors such as TCs, RTDs and linear transducers using the
terminal boards described later in this section.
High voltage isolation capability
Supports TCs, RTDs and linear voltage & current signals
LED status indicator
DIN rail/panel mount
Connects to analog input terminal board via 50-pin SCSI
cable