Instruction Manual

PPC-2000 User’s Guide Chapter 2: Hardware Installation
Doc.# 30002-00 Rev 2.3 Watlow Anafaze 21
Table 2.6 PPC-2030 Analog Output Jumpers
* Listed values are maximum ranges. Other ranges within these
limits may be selected in software.
PPC-2040 Jumper Settings
Each of the counter inputs on the PPC-2040 can be configured
for single phase or quadrature input. Jumper positions
determine the counter input configuration. To select single
phase or quadrature, see Table 2.7 and Figure 2.6 to determine
which jumper to set and appropriate position.
Table 2.7 PPC-2040 Counter Input Jumpers
Figure 2.6 PPC-2040 Jumper Settings
Analog
Output
Jumper #
i (current)
position*
V (volt)
position*
1 JU4 0-20mA 0-10Vdc
2 JU3 0-20mA 0-10Vdc
3 JU2 0-20mA 0-10Vdc
4 JU1 0-20mA 0-10Vdc
Counter
Input
Jumper
PPC-2040
Single Phase
Position
Quadrature
Position
1 JU1 A B
2 JU2 A B
A B
A B
JU2
JU1