Instruction Manual

Chapter 2: Hardware Installation PPC-2000 User’s Guide
22 Watlow Anafaze Doc.# 30002-00 Rev 2.3
PPC-205x Jumper Settings
Each of the analog outputs on the PPC-205x modules may be
configured either as a voltage output or a current output. A
mixture of current and voltage outputs may be used on a
particular module. The jumpers only determine if the output
signal is current or voltage. The actual span of the signal is
software selectable. See Heat/Cool Output Type in Channels
section on page 119 for the various analog output signal
settings.
To configure an output, see Table 2.8 on page 22 and Figure 2.7
on page 23 to determine which jumper to set. Set the jumper in
the indicated position and orientation.
Table 2.8 PPC-205x Analog Out Jumpers
* Listed values are maximum ranges. Other ranges within these
limits may be selected in software.
Analog
Output
Jumper
PPC-2050
Jumper
PPC-2051
i (current)
Position*
v (voltage)
Position*
1 JU1 JU1 0-20mA 0-10Vdc
2 JU2 JU3 0-20mA 0-10Vdc
3 JU3 JU5 0-20mA 0-10Vdc
4 JU4 JU7 0-20mA 0-10Vdc
5 JU5 n/a 0-20mA 0-10Vdc
6 JU6 n/a 0-20mA 0-10Vdc
7 JU7 n/a 0-20mA 0-10Vdc
8 JU8 n/a 0-20mA 0-10Vdc