Instruction Manual

Adaptive Addendum PPC-2000 User's Guide
0600-0049-0001 rev C Watlow Anafaze 4
a. In the PV Source field, choose the input that you want to
monitor or use as feedback for closed-loop control.
b. In the
Heat Output Dest and/or Cool Output Dest fields,
choose the outputs that you want to use for closed-loop control.
c. Choose a
Heat/Cool Output Type for each output.
d. Set the
Heat/Cool Cycle Time for any outputs with Heat/ Cool
Output Type
set to Time Prop.
4. On the
Digital I/O spreadsheet:
a. Set the
Direction for each I/O point to be used for control to
Output.
5. On the
Channels spreadsheet:
a. For channels other than the adaptive ones, if both heat and cool
outputs are used, set the
Spread.
b. For each channel that will perform adaptive control, for the
Control Type, choose Adaptive.
c. Set the
Set Point to the desired value at least 40 engineering
units (typically degrees) above the process variable.
d. Set the
Control Mode to Auto to begin adaptive closed-loop
control.
NOTE: Only channels 1 to 8 can be selected for adaptive control.