Instruction Manual

Chapter 2: Hardware Installation PPC-2000 User’s Guide
72 Watlow Anafaze Doc.# 30002-00 Rev 2.3
Figure 2.60 Relay Output Connections on a
PPC-2062: Outputs 1 and 2 Shown
Table 2.23 Relay Output Connections on
PPC-206x Digital Output Modules
1
The AnaWin3 name is shown for the Digital Out module with address 41 on the
first PPC-2000 in the system. See Digital I/O on page 132 for a full explanation
of Digital I/O naming.
Module
I/O Number
Digital Out Module
Connections
AnaWin3 Name
(Dig I/O Spread-
sheet)
1
PPC-2061
PPC-2062
Out Com
Digital Out 1 1 C1 1A 1B PPC1:DO 41.1
Digital Out 2 2 C1 2A 2B PPC1:DO 41.2
Digital Out 3 3 C1 3A 3B PPC1:DO 41.3
Digital Out 4 4 C1 4A 4B PPC1:DO 41.4
Digital Out 5 5 C1 5A 5B PPC1:DO 41.5
Digital Out 6 6 C1 6A 6B PPC1:DO 41.6
Digital Out 7 7 C1 7A 7B PPC1:DO 41.7
Digital Out 8 8 C1 8A 8B PPC1:DO 41.8
Digital Out 9 9 C2 n/a n/a PPC1:DO 41.9
Digital Out 10 10 C2 n/a n/a PPC1:DO 41.10
Digital Out 11 11 C2 n/a n/a PPC1:DO 41.11
Digital Out 12 12 C2 n/a n/a PPC1:DO 41.12
Digital Out 13 13 C2 n/a n/a PPC1:DO 41.13
Digital Out 14 14 C2 n/a n/a PPC1:DO 41.14
Digital Out 15 15 C2 n/a n/a PPC1:DO 41.15
Digital Out 16 16 C2 n/a n/a PPC1:DO 41.16
AC or DC
Source
Load
Relay 1
Relay 2
1A
1B
2A
AC or DC
Source
2B
Load
PPC-2062
L2 (AC)
L2 (AC)
L1 (AC)
L1 (AC)