2 WATLOW Series 365 User’s Manual
Description
Specifications
The Series 365 is a 1/16 DIN factory-selectable ana-
log latching limit, ON/OFF or PI control. The control
operates from a thermocouple or RTD input and is
available in several thermocouple ranges including
Types J, K, T, R, S or Platinel II thermocouple.
The 365 has an integral setpot with a front panel
reset switch, and a front panel LED indicator for
output status. In addition to the internal reset
switch, a customer supplied remote reset switch
can be used with the limit control only.
Factory-selectable options include ON/OFF, PI or
latching limit control modes, and auto or manual
reset on power loss. In ON/OFF or PI mode, heat
or cool operation is user-selectable.
The compact size of the controller allows more flexibility
in applications where space is a problem, such as
bench top equipment. The 365 is tested to meet NEMA
4X standards for water and corrosion resistance.
Control Mode
Heat or cool, user selectable
ON/OFF
Switching hysteresis: Typically 3°F/1.7°C
•PI(Time proportional with automatic reset)
Proportional band adjust: Typically
5 to 50°F/2.8 to 27.8°C
Cycle time, fixed: Typically 6 seconds
Automatic reset, fixed: Typically
0.25 repeats/minute
Limit
Latching
High or low, factory selectable
Internal reset switch and/or customer supplied
remote reset switch. Automatic or manual reset
on power loss (factory selectable).
Operator Interface
Sealed membrane front panel, NEMA 4X
LED indication of limit condition or status of load
Integral Setpot
Dial scale calibrated to compensate for sensor
non-linearities
Dual °F & °C scales
Input
Thermocouple or RTD available
Thermocouple may be grounded or ungrounded
Thermocouple, automatic cold junction
compensation
RTD input 2 or 3 wire, platinum 100@ 0°C cali-
brated for #3850 (DIN): 0.003850/°C or #3916
(JIS) 0.003916/°C curve.
Thermocouple and RTD sensor break protection
de-energizes output to protect system.
Output
Solid state relay with contact suppression, Form
A, 0.5A @ 24VAC min., 264VAC max., opto iso-
lated zero-cross switching. Minimum offstate
impedance is 20K. Only available with ON/OFF
or PI control.
Open collector, switched DC signal provides a
minimum turn ON voltage of 3VDC into a mini-
mum 500 load; maximum ON voltage not
greater than 32VDC into an infinite load. Only
available with ON/OFF or PI control.
Electromechanical relay, Form C, 5A @
120/240VAC. Minimum offstate impedance is
20K. Warranted to 100,000 cycles.
Electromechanical relay, Form C, 10A @
120/240VAC. Minimum offstate impedance is
20K. Warranted to 100,000 cycles.
Solid state relay without contact suppression,
Form A, 0.5A @ 24VAC min., 264VAC max., opto
isolated zero-cross switching. Minimum offstate
impedance is 31M. Only available with ON/OFF
or PI control.
Power
Factory selectable
100VAC, ±10%; 50/60 Hz, ±5%
120VAC, -15%, +10%; 50/60 Hz, ±5%
208VAC, -15%, +10%; 50/60Hz, ±5%
240VAC, -15%, +10%; 50/60 Hz, ±5%
4VA power consumption
Agency Approvals
UL, CSA and FM pending
NEMA 4X rating, pending
Terminals
#6 compression universal head screw terminals,
accepts 20-14 gauge wire
Accuracy
Calibration accuracy & sensor conformity: ± 1%
of span maximum, at 77°F ± 5°F (25°C ± 3°C)
ambient and rated line voltage.
Accuracy span: 1000°F/540°C minimum
Set point accuracy: ± 3% of span maximum
Temperature stability: Typically ± 5µV / °F ambi-
ent for thermocouple. Typically < 1°F from 32 to
130°F for RTD.
Voltage stability: ± 0.01% of span /% of rated line
voltage.
Operating Environment
32 to 130°F (0 to 55°C)
0 to 90% RH, non-condensing
Storage temperature: -40° to 158°F (-40° to 70°C)