MC100 DeviceNet OM 1.15 EN Version: 1.04 Page 35 of 43
8 Alarm and warnings
8.1 Alarms handling
When MC100 is in Alarm state, the only possible action is to reset the alarm. Only applies if the alarm
causes are removed, otherwise the alarm will re-appear at the next attempt.
Alarms are cleared one-by-one, starting top down – meaning lowest number first.
8.1.1 Module Alarms
Alarm no.
Alarm description Action
0 No pending alarms
1
No pumps connected during
power up
Check connections /power to pumps
2
Connection to one or more
pumps lost
Check connections /power to missing pump
3
Connected pumps not equal to
last time
Configuration changed – Investigation or new
initialization must be done
4
Attempt to access not
connected pump
5 Reverse direction not available
Pump command Bit 5: Direction
set for one direction pump
6
Unstable FlexNet: Check
pumps
9
Difficult to trigger, but observe flashing ONLINE
indicator, which indicate the same fault.
7
FRAM storage failure: Restart
or Reset
8
Mode change not completed:
check pumps
Changing mode was not possible, check pump
versions, if change was to parallel or serial mode
9
Missing or defect Anybus
CompactCom Module
No Alarm string available, because module not working
10 Reserved
11 Run length limit Run length less than 5 or more than 16777215 steps
12 Parameter process error
Failed to transfer parameters from PLC to
pumps/FRAM
13-16 Reserved
NN
FB module not Ready
10
Internal MC100 module check, possible replacement of
module.
Pump alarms
20 Dispense not finished Dispensing has stopped before finishing.
21 Tube bridge off at dispense start Dispensing or pumping cannot start
22 Tube bridge off while dispensing Dispense not finished
23 Tube bridge off at pumping start Trying to start pumping with tube bridge off
24 Tube bridge off while pumping Removing tube bridge while pumping
9
Expected to be implemented in a later version
10
Alarm is only displayed with the 2 LED’s on MFSC module – both flashes RED/ORANGE.