Installation Instructions

2
WIRING
When wiring the LMFS-601-W to either a DALI driver or LMFI-111 Fixture
Interface, use only solid core wire (18-20 AWG).
NOTE: The middle connector is unused on the sensor.
LMFI-111
Ballast or LED Driver
DA–
DA+
DIM–
DIM+
Neutral
Load
Neutral
Line
LMFS-601-W with 0-10V LED Driver and LMFI-111 Fixture Interface
LMFS-601-W with DALI Driver
DA–
DA+
Neutral
Line
DALI Driver with integrated
self-powered DALI link
SENSOR COVERAGE
The LMFS-601-W provides a 360° coverage pattern. The coverage shown represents maximum coverage for walking motion at a
mounting height of 8 feet. The lens is designed for mounting heights ranging 8’–12’ and covers up to 300 sq/ft of space.
0’4'10' 8'
4'
8'
0'
4'
8'
10'
10'
6' 2' 2' 4' 6' 8' 10'
5'
8'
0’
0’ 5'5'
2.5'
10' 10'
Coverage Top View @8ft Coverage Side View
WARNING: TURN THE POWER OFF AT
THE CIRCUIT BREAKER BEFORE WIRING.
Sensor Placement
Mount sensor at least 6’ away from air supply.
Avoid obstacles that block sensor’s line-of-sight.
Sensor
1
Carrier
Sleeve
Collar
Fixture
2
3
Installation
The LMFS-601-W comes equipped with a carrier a sleeve and collar in which it snaps into during installation into the fixture.
The carrier sleeve fits into industry standard 1/2” knockouts and/or a 7/8” hole. The carrier sleeve is intended to be mounted into lighting
fixtures or directly into ceiling tiles.
1. To install the carrier sleeve into the desired knockout, apply pressure and turn counterclockwise until the carrier sleeve is flush
with the mounting application.
2. Screw the collar onto the inside of the carrier sleeve threading.
3. Slide the sensor into the carrier sleeve until it securely snaps into place.