Onix Tubing Submittal

ONIX TUBING SPECIFICATIONS
Nominal Tubing Size Maximum Bend Fluid Capacity
Quantity Product Model No. I.D. O.D. Lengths Radius Per 1,000 ft.
3/8" Onix 086061 3/8" 11/16" 200 ft.
1
3" 6.25 gal.
1/2" Onix
086081
1/2"
7/8"
300 ft.
2
4"
10.25 gal.
5/8" Onix 086101 5/8" 1" 600 ft.
2
5" 16.00 gal.
3/4" Onix 086121 3/4" 1-1/8" 350 ft.
2
6" 25.00 gal.
1" Onix
086161
1"
1-3/8" 200 ft.
3
8"
43.50 gal.
PRODUCT DESCRIPTION
Onix is a polymer-rich, multi-layer, industrial-grade hose used for
hydronic heating and snowmelting applications. It contains five
distinct structural layers. The Durel inner tube is a peroxide-cured,
cross-linked EPDM (Ethylene Propylene Diene Monomer). This layer is
wrapped with a ductile 00 grade aluminum oxygen barrier, called
AlumaShield. A contour layer of Durel (EPDM) is extruded over the
AlumaShield. Spiral reinforcing cords of Aramid fibers are applied
over the contour layer. This reinforcing is covered with the outer
HiGuard cover composed of sulfur-cured, cross-linked EPDM.
OPERATING TEMPERATURE AND PRESSURE
Onix has a maximum working temperature of 180°F at 100 psi.
Burst pressure is greater than 800 psi at 70
°
F; greater than 600 psi
at 180°F.
ONIX ACCESSORIES
Several accessories are associated with Onix. Please reference other
Watts Radiant documents for more information.
APPROPRIATE APPLICATIONS
Onix is used for hydronic heating and snowmelting applications.
Please reference the Onix Master Specification, RadiantWorks
®
Reports and installation manual and guidelines for information
concerning design, sizing, installation and application.
MANIFOLDS
Manifolds for Onix are made of copper, cast brass, and stainless
steel, and are available in a variety of types and sizes. Refer to
Watts Radiant’s Onix Manifolds Submittal for more details (see
reverse).
CONNECTIONS
Onix is connected to the Onix manifolds with barbed Onix fittings
using Watts Radiant SelfTite™ or TorqueTite™ clamps. SelfTite
clamps should be installed using SqueezeTite™ pliers.
INSTALLATION
Onix must be installed in accordance with all Watts Radiant installa-
tion procedures, including information provided in Watts Radiant’s
Onix installation manual and guidelines. Refer to RadiantWorks
design information and design plans.
CODES, LISTINGS, AND STANDARDS
ASTM: Onix is tested to relevant portions of ASTM
standards.
BOCA: Provide radiant tubing carrying the BOCA
certification mark, as approved by the BOCA research
report number 95-47.1.
Uniform Plumbing Code: Provide radiant tubing carrying
the UPC certification mark, as approved by the Interna-
tional Association of Plumbing and Mechanical officials.
RPA: Install radiant tubing in compliance with the
Standard Guidelines for Radiant Panel Installations, as
approved by the Radiant Panel Association.
Copyright © 2005 Watts Radiant, Inc. Onix/Onix Manifolds Submittal LIT#ONIXSUB0705 This submittal supersedes all previous Onix Submittals. Effective 07/12/2005
1
Available in 20-ft. increments.
2
Available in 25-ft. increments.
3
Available in 100-ft. increments.
HiGuard™
Industrial Cover
Aramid Fiber
Reinforcing
AlumaShield™
Oxygen Barrier
Durel™
Inner Tubing
Contour
Extrusion Layer
4500 E. Progress Place
Springfield, MO 65803-8816
800-276-2419/417-864-6108 (Phone)
417-864-8161 (Fax)
www.wattsradiant.com
PROJECT NAME: ____________________________________________________________________________________
WATTS RADIANT REPRESENTATIVE: ____________________________________________________________________
Unit Tag No.:____________________________ Order No.: ________________________ Date: ________________
Engineer: ______________________________ Submitted by:______________________ Date: ________________
Contractor: ____________________________ Approved by: ______________________ Date: ________________
Onix