Technical Specifications

Standards
ASSE 1022
Installation: The valve can be installed horizontally or vertically
(flow up or flow down). The valve should be installed so that
the strainer and the valve are accessible for service and main-
tenance. In the event the second check valve becomes fouled,
the vent port opens to atmosphere and water and CO2 Gas
is discharged. Connect a vent discharge line to the vent outlet
of the SD3 and vent to a safe place of disposal with adequate
ventilation in order to prevent personal injury or damage. The
valve should be installed such that water discharge from the
vent will not cause damage to the surrounding equipment or
property.
The device should not be installed inside a wall or in a con-
cealed location. Copper tubing shall not be used on the down-
stream side of the backflow preventer used in carbonated
systems. Copper tubbing can be used downstream for non
carbonated systems such as coffee makers.
Dimensions (approx.)
kPa psi
207 30
172 25
138 20
103 15
69 10
34 5
0 0
0 .21 .41 .68 1 1.2 1.5 1.6 1.8 gpm
0 .8 1.5 2.6 3.8 4.6 5.7 6.1 6.8 lpm
Pressure Drop
Flow
Pressure Drop
Flow
kPa psi
207 30
172 25
138 20
103 15
69 10
34 5
0 0
0 .25 .61 1.7 2.2 2.4 2.5 gpm
0 .95 2.3 6.5 8.4 9.1 9.5 lpm
A
C
D
B
Across
Corners
1
4" (8mm) SD-3
Water Supply Installations
Post Pumping Installations
Valve
Water
Supply
Strainer
SD3 Backflow
Preventer
Beverage
Dispenser
Plastic
Pipe
Vent Discharge Line
Valve
Filter
Water
Supply
Strainer
SD3 MF-LS
Backflow Preventer
Carbonated
Beverage
Dispenser
Vent Discharge Line
CO
2
gas in
vented area
Carbonator
H
2
0 and CO
2
Pump
Pressure/Temperature
Max. Pressure: 150psi (10 bar)
Max. Temperature: 130°F (54°C)
Typical Installations
3
8" (10mm) SD-3
SIZE (DN) PART # ASSEMBLY ORDER CODE DIMENSIONS
A B C D
in mm in. mm in mm in mm in mm
1
4" 8 SD3-MN 0061652 4
1
2 114 1
1
16 27 1
7
8 48 1
3
4 44
1
4" 8 SD3-MF 0061653 4
3
8 111 1
1
16 27 1
7
8 48 1
3
4 44
3
8" 10 SD3-MN 0061656 4
1
2 114 1
1
16 27 1
7
8 48 1
3
4 44
3
8" 10 SD3-MF 0061657 4
1
2 114 1
1
16 27 1
7
8 48 1
3
4 44
1
4" 8 SD3-FN 0061666 4
1
2 114 1
1
16 27 1
7
8 48 1
3
4 44
3
8" 10 SD3-FN 0061667 4
1
2 114 1
1
16 27 1
7
8 48 1
3
4 44
=3
8" 10 SD3-MF-LS 0061671 2
5
8 67 1
1
16 27
=
For use on post pumping installations only.
Capacity
NOTICE
ES-SD3 1624 © 2016 Watts
USA: Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com