Installation Sheet

DO NOT REMOVE
TAG FROM VALVE
WARNING:
IMPORTANT
SAFETY INSTRUCTIONS
FAILURE TO COMPLY WITH
THESE INSTRUCTIONS CAN RESULT IN SERIOUS PERSONAL
INJURY OR DEATH AND/OR SEVERE PROPERTY DAMAGE.
This device is designed for emergency safety relief and shall not be
used as an operating control. Valves should not be used on coal or
wood boilers having an uncontrolled BTU heat input.
Safety relief valves shall be connected to the top of the boiler with
the valve in the vertical position, either directly to a tapped or
flanged opening in the boiler, to a fitting connected to the boiler by
a close nipple, to a Y base, to a valveless header, connecting water
outlets on the same boiler, or to a valveless water pipe between
adjacent boilers.
WARNING: To avoid water damage or
scalding due to valve operation, discharge line must be
connected to valve outlet and run to a safe place of dis-
posal.
Discharge line must be as short as possible and be the
same size as the valve discharge connection throughout its entire
length. Discharge line must pitch downward from the valve and ter-
minate at least 6" (152mm) above the floor drain where any dis-
charge will be clearly visible. The discharge line shall terminate
through plain (unthreaded) pipe. Discharge line material must con-
form to local plumbing code or A.S.M.E. requirements. No shutoff
valve shall be installed between the relief valve and boiler, or in the
discharge line.
WARNING: If discharge occurs, CALL A PLUMBER IMMEDIATE-
LY. A licensed contractor must evaluate the system and determine
the cause of discharge and correct the cause immediately.
Discharge may indicate that an unsafe pressure condition exists
within the tank which requires immediate attention by a licensed
plumbing contractor.
WARNING: Following installation, the valve lever MUST be operated
AT LEAST ONCE A YEAR by the boiler owner to insure that water-
ways are clear. Certain naturally occurring mineral deposits may
adhere to the valve, rendering it inoperative. When manually oper-
ating the lever, water will discharge and precautions must be taken
to avoid contact with hot water and to avoid water damage.
BEFORE operating lever, check to see that a discharge line is con-
nected to this valve directing the flow of hot water from the valve to
a proper place of disposal otherwise personal injury may result. If
no water flows, valve is inoperative. CALL A PLUMBER IMMEDI-
ATELY.
SEE OTHER SIDE FOR IMPORTANT INFORMATION
NOTICE
This valve must be installed by a licensed plumbing
contractor in accordance with these instructions.
Repair or alteration of valve in any way is prohibited by
national safety standards/local codes.
This boiler water safety relief valve is for protection
against excessive water pressure caused by thermal
expansion of the water. Although the valve also has
an emergency BTU steam discharge capacity if run-
away firing conditions occur, do not use for continu-
ous steam service.
WARNING: REINSPECTION OF SAFETY RELIEF
VALVES: Safety Relief Valves should be rein-
spected AT LEAST ONCE EVERY THREE YEARS by
a licensed plumbing contractor or authorized inspec-
tion agency, to insure that the product has not been
affected by corrosive water conditions and to insure
that the valve and discharge line have not been
altered or tampered with illegally. Certain naturally
occurring conditions may corrode the valve or its
components over time, rendering the valve inopera-
tive. Such conditions are not detectable unless the
valve and its components are physically removed
and inspected. Do not attempt to conduct this
inspection on your own. Contact your plumbing
contractor for a reinspection to assure continuing
safety.
FAILURE TO REINSPECT THIS VALVE AS DIRECT-
ED COULD RESULT IN UNSAFE PRESSURE BUILD-
UP WHICH CAN RESULT IN SERIOUS INJURY OR
DEATH AND/OR SEVERE PROPERTY DAMAGE.
Watts Regulator Co. www.watts.com