Install Instructions

2
Specifications
• Maximum Operating Pressure ............................. 125 psig (861 kPa)
• Maximum Hot Water Temperature .......................... 200°F (93°C)
Minimum Hot Water Supply Temperature ..................... 5°F (3°C) Above Set-Point*
• Temperature Adjustment Range** ........................... 90 - 180°F (32 - 82°C)
• Hot Water Inlet Temperature Range ......................... 120 - 180°F (42 - 82°C)
• Cold Water Inlet Temperature Range ........................ 40 - 80°F (4 - 27°C)
• Listing ................................................ ASSE 1017, IAPMO CUPC
• Approval Standards ..................................... ASSE 1017, CSA B125.3
* With Equal Pressure
** Low limit can not be less than the cold water temperature. For best operation, hot water should be at least 5°F (3°C)
above desire set point.
Basic Installation
ATTENTION INSTALLER: After installation,
please leave this Instruction Sheet for
occupant’s information.
Minimum Flow Requirements to
Maintain Set Temperature
for N170-M3 or LFN170-M3 Series
Valve Size gpm
3
4
" thru 2" (20-50mm) 3 to 7 (11 to 26.5 lpm)
Shutoff Valves
(on both hot
and cold inlets)
Check Valves
(on both hot and
cold inlets)
Storage
Tank
8" to 12"
ASME Pressure
Relief Valve
Cold
† N170-M3
or LFN170-M3
Tempering
Valve
Water Heater
or
Hot Water Boiler
Drain
To Model
L111, LFL111, MMV or LFMMV
CSA/ASME T&P Valve
Cold
180°F
Thermometer
Tempered 140°F *†
From Cold Supply
To Fixture
Lock Nut
Temperature
Adjusting Screw
Cold
Water
Hot
Water
Actuator
NOTE: Heat trap is recommended.
† Valves listed to ASSE Standard 1016, 1069
or 1070, such as the Watts L111, LFL111,
USG, LFUSG, MMV, or LFMMV should be
used at point of delivery.