Spec Sheet

For Non-Health Hazard Applications
ES-007
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
–––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES
FOR LOCAL INSTALLATION REQUIREMENTS
Now Available
WattsBox Insulated Enclosures.
For more information, send for literature ES-WB.
Series 007
Double Check Valve Assemblies
Sizes:
1
2" – 3" (15 – 80mm)
Series 007 Double Check Valve Assemblies shall be installed at
referenced cross-connections to prevent the backflow of pollut-
ed water into the potable water supply. Only those cross-con-
nections identified by local inspection authorities as non-health
hazard shall be allowed the use of an approved double check
valve assembly.
Check with local authority having jurisdiction regarding vertical
orientation, frequency of testing or other installation requirements.
The valve shall meet the requirements of ASSE Std. 1015 and
AWWA Std. C510. Approved by the Foundation for Cross-
Connection Control and Hydraulic Research at the University of
Southern California.
Features
Ease of maintenance — only one cover
Top entry
Replaceable seats and seat discs
Modular construction
Compact design
Cast bronze body construction —
1
2" – 2" (15 – 50mm)
Fused epoxy coated cast iron body — 2
1
2" – 3" (65 – 80mm)
Top mounted ball valve test cocks
Low pressure drop
No special tools required for servicing
1
2" – 1" (15 – 25mm) have tee handles
Specifications
A Double Check Valve Assembly shall be installed at each
noted location. The assembly shall consist of two positive seat-
ing check modules with captured springs and rubber seat
discs. The check module seats and seat discs shall be
replaceable. Service of all internal components shall be through
a single access cover secured with stainless steel bolts. The
assembly shall also include two resilient seated isolation valves;
four top mounted, resilient seated test cocks. The assembly
shall meet the requirements of ASSE Std. 1015 and AWWA
Std. C510. Approved by the Foundation for Cross-Connection
Control and Hydraulic Research at the University of Southern
California. Assembly shall be a Watts Regulator Company
Series 007.
3
4" (20mm) 007M3QT
2" (50mm) 007M1QT HC
Test Cocks
First Check
Module Assembly
The 007 Series features a modular design concept which facilitates
complete maintenance and assembly by retaining the spring load.
Second Check
Module Assembly
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.