Installation Manual

Santa Clara, CA 95050
800.879.8585
Installation Instructions
Specifications
Voltages:
PW-301 & PW-302. . . . . . . . . . . . . . . . 120/277VAC, 50/60Hz
PW-301-347 & PW-302-347. . . . . . . . . . . . 347VAC, 50/60Hz
Load Limits for relay 1:
@120VAC..1000W tungsten, ballast, E-ballast, LED, 1/4 HP
@277VAC.......... 1200W ballast, E-ballast, LED, 1/4 HP
@347VAC................... 1500W ballast, LED, 1/4 HP
Load Limits for relay 2:
@120VAC...800W tungsten, ballast, E-ballast, LED, 1/6 HP
@277VAC.......... 1200W ballast, E-ballast, LED, 1/6 HP
@347VAC................... 1500W ballast, LED, 1/6 HP
Time Delay Adjustment ....................5 to 30 minutes
Walk-Through Mode .... 3 minutes if no activity after 30 sec.
Test Mode .................. 10 min. with 5 sec. time delay
PIR Adjustment ..............................High or Low
Light Level Adjustment ......................8fc to 180+fc
Alerts ......................Selectable Audible & Visual
Optional Neutral . . . . . . . . . . . . . . . . . . . . . . . . . . . . .All models
Multi-Way Capability . . . . . . . . . . . . . . . . . . . . . . . . . All models
Terminal screw torque . . . . . . . . . . . . . . . . 16 lbf-in (18 kgf-cm)
PW-301 PW-301-347 PW-302 PW-302-347
PW-301/PW-301-347
PW-302/PW-302-347
Passive Infrared Multi-Way Wall Switch
Occupancy Sensor