Specifications
RT9 Powershelf    Rectifier Technologies 
158-1806-01.doc 
11  2-Mar-06 
The switched battery cables (-ve in a –48V system) terminate on the copper bars of the 
battery distribution module (item 2 in Figure 2.3), while the battery return cables terminate 
on the common return bar (item 3 in Figure 2.3). The battery distribution module can be 
configured for up to four battery strings with the appropriate number of return cable 
termination points being available on the common bar. 
Load switched connections can be made either through the optional load circuits that can 
be installed in the battery distribution module, or as bulk load connections to the main 
rectifier busbars. The load return is then terminated either on the common return bar or on 
the rectifier common busbars. External DC distribution feed connections are made as a 
bulk load connection. 
In many cases, the AC distribution is external to the Powershelf. The AC feed should be 
wired as individually protected feeds for each rectifier (recommended and preferred) to 
provide discrimination of fault protection devices. Alternatively, a single AC supply (1φ or 
3φ) can be used, but there will not be any discrimination and if one unit generates a fault, 
the power to all rectifiers will be removed. Where the AC distribution is integrated into the 
Powershelf, each rectifier feed is individually protected and the installer is only required to 
connect a single AC supply (1φ or 3φ) to the AC DIN rail terminations. 
Remote communications and alarm relay cabling connects to the top rear cover. Allow 
enough free cable to permit the top cover to hinge open or to remove the Powershelf from 
the front of the rack for maintenance. 
3.3 Mains Connections 
Figure 3.4 










