Specifications
RT9 Powershelf    Rectifier Technologies 
158-1806-01.doc 
13  2-Mar-06 
3.3.3 3 phase star – individual protected external feeds 
Remove the link connecting the active terminals “A” together. Connect one phase wire per 
“A” terminal. Connect the neutral wires to the common neutral terminals. 
Figure 3.6 
3.3.4 3 phase delta – individual protected external feeds 
Phase-to-phase (208VAC) connections require that the AC terminal blocks for the neutral 
be replaced with individual active line terminals. Then for each rectifier, the two AC lines 
can be wired to the appropriate phases. This configuration needs to be specially ordered 
to ensure that the correct number of terminal blocks is loaded. The system will be shipped 
with links in the active terminal blocks to configure the system as single phase (but for 
phase-to-phase connection). Note that double fused versions of RT9 must be ordered. 
To wire as 3 phase delta, remove the links connecting the active terminals together, and 
connect each phase-to-phase pair of wires to a set of “A” and “C” terminals. Phase rotation 
is not important. Double pole circuit breakers are required.
Figure 3.7 