3.3.5  Surge protection requirements 
The rectifiers are internally protected for surges up to 6kV/3kA. For higher levels of 
protection, particularly for sites with high incidence of lightning or switching surges, 
additional surge protection is required on the AC feed to the Powershelf. Typically surge 
arrestors with a 10kA-40kA rating are required with the highest level of protection being 
provided when arrestors are connected between phase-netural (x3 phases) and between 
phase/neutral-earth (x 3 phases). 
Other arrangements (for 3-phase “star”) with similar levels of protection are also possible 
as shown below. The voltage rating of the arrestor should be selected based on the 
maximum AC voltage likely to appear on the line. The arrestor should limit the voltage to 
<1200V – 1400V at the rated maximum pulse current. 
Figure 3.8 