Specifications
RT9 Powershelf    Rectifier Technologies 
158-1806-01.doc 
21  2-Mar-06 
Note: If the country in which you intend to use the Integrated Modem is not listed, a 
generic code ‘99’ or ‘FD’ can be tried. 
Country / Approval  Code  Country / Approval  Code  Country / Approval  Code 
Argentina   Y  07  Iceland    Y  FD  Philippines   Y  B5 
Australia   Y  09  India     Y  99 (53)  Poland     Y  FD (8A) 
Austria     Y  FD (0A)  Indonesia   Y  99  Portugal   Y  FD (8B) 
Belgium   Y  FD (0F)  Ireland   Y  FD (57)  Russia   Y  FD (B8) 
Brazil     Y  16  Israel     Y  B5  Singapore   Y  9C 
Canada    Y  B5  Italy     Y  FD (59)  Slovakia   Y  FD 
Chile     Y  99  Japan     Y  00  Slovenia   Y  FD 
China     Y  B5 (26)  Korea     Y  B5 (61)  South Africa   P  9F 
Cyprus     Y  FD  Latvia     Y  FD  Spain     Y  FD (A0) 
Czech Republic Y  FD  Lichtenstein   Y  FD  Sweden   Y  FD (A5) 
Denmark   Y  FD (31)  Lithuania   Y  FD  Switzerland   Y  FD (A6) 
Estonia   Y  FD  Luxembourg   Y  FD  Taiwan    Y  FE 
Finland    Y  FD (3C)  Malaysia   P  6C  Thailand  ….Y  B5 
France     Y  FD (3D)  Malta     Y  FD  Turkey   Y  FD 
Germany   Y  FD (42)  Mexico     Y  B5 (73)  United Kingdom  Y  FD (B4) 
Greece    Y  FD  Netherlands   Y  FD (7B) United States   Y  B5 
Hong Kong   Y  99 (50)  New Zealand   Y  7E 
Hungary   Y  FD  Norway   Y  FD (82) 
Approval: Y = yes ; P = in progress 
Approval status in the table is indicated as declared by manufacturer on 15/12/2005. 
3.12  Battery/Load Distribution Module 
The battery/load distribution module is supplied with a standard number of battery strings 
pre-wired. Optional extra battery or load connections may also have been supplied and 
pre-wired from the factory as ordered. Servicing fuses, circuit breakers or adding optional 
battery/load connection kits after initial installation and commissioning requires that the lid 
of the battery distribution module be removed and top access can be gained. The lid is 
held in place by two M3 screws at the front and will slide forward out of the Powershelf 
once the screws are removed. If top access cannot be gained, the entire module can be 
removed from the front after disconnecting and isolating the battery/load connections and 
removing the single M5 mounting screw at the rear. 
To add a battery string kit, mount the circuit breaker, DC current transducer, output busbar 
and wiring in the next logical battery number position as shown in Figure 3.15. Connect 
the current transducer signal cable to the appropriately labelled connector on the circuit 
board. Finally, make sure the jumper link for the same numbered battery/load circuit alarm 
is linked for “BAT”. (see Figure 3.16). 
To add a load connection kit, connect the DC bus side of the circuit breaker directly to the 
M6 stud on the DC bus side of the LVDS. Starting with the “Battery 4” position, mount the 
output busbar, circuit breaker and wiring. Set the jumper link for the same numbered 
battery/load circuit alarm to “LOAD”. (see Figure 3.16). 










