Specifications
RT9 Powershelf    Rectifier Technologies 
158-1806-01.doc 
44  2-Mar-06 
8. Specifications 
Input AC 
Voltage 
Universal AC 85-300VAC (L-N. 1φ, or 3φ-star, 3φ-delta [option]. 
Fully protected up to 440VAC (L-N) 
Inrush Current  <9A RMS per rectifier 
THD  Line Harmonics meet EN61000-3-2 
Power Factor  >0.98 for >50% output power 
Output DC 
Voltage  -48VDC systems, adjustable range 42.0V to 59.5V 
+24VDC systems, adjustable range 21.0V to 30.0V 
Current Limit  30A per 48V rectifier module, 60A per 24V module. Fully adjustable 
Power Limit  1400W per rectifier module 
Efficiency  >90% at 100% output power for 48VDC systems 
>88% at 100% output power for 24V systems 
Regulation  +/- 1% or better over line, load and temperature 
Noise  <1mV RMS Psophometrically weighted 
<32dBrnC Voiceband 
<10mV RMS and <100mV peak-to-peak (10kHz-100MHz) 
Protection 
Short Circuit  Can sustain short circuit at output terminals indefinitely 
Reverse Battery Polarity  Internal fuse at output of SMR, integral battery circuit breakers and detection/disconnection 
circuitry 
High Voltage Shutdown  Rectifier shuts down if output exceeds programmed overvoltage limit 
Electrostatic Discharge (ESD)  IEC 61000-4-2 (Level 4: Air 15kV, Contact 8kV) 
AC Surge  IEC 61000-4-4 (EFT), Level 4 
IEC 61000-4-5 (Impulse), Level X: 6kV/3kA 
IEC 61000-4-12 (Ringwave), Level X: 6kV/500A 
RF Immunity  IEC 61000-4-3 (Radiated), Level 4 
IEC 61000-4-6 (Conducted), Level 3 
RF Emissions  CISPR 22 Class B, (Conducted & Radiated) 
Environmental 
Operating 
-40°C to +70°C 
Full Power 
-40°C to +55°C 
Derated Operation 
50% power at +70°C 
Storage/Transport 
-40°C to +70°C 
Humidity  0 to 100% relative humidity, condensing 
Acoustic Noise  < 60dB (A weighting) 
Mechanical Dimensions 
Width 483mm  (19”) 
Depth 355mm  (14”) 
Height*  88mm – 352mm (3.4” – 13.6”) *depending on configuration 
Agency Compliances 
Safety  IEC 60950, UL/CSA 60950 
EMC  ETSI EN 300 386 V1.3.2 (2002-12) 
Environmental  ETSI EN 300 019 
Wave Communications Pty Ltd 
Unit 5, 97 Jijaws St
Sumner Park QLD 4074 
TEL: 07 3279 0600
FAX: 07 3279 0544
EMAIL: 
sales@wavecomeng.com.au
WEBSITE: www.wavecomeng.com.au