Installation guide
SmartSensor 105 User Guide – Wavetronix LLC 9/20/07  - - 
36
mounted next to the sensor. In this case, the homerun connection establishes one RS-485 
channel over the normal white/blue wire pair and another RS-485 channel over the 
yellow/violet wire pair. An additional Click! 304 is needed to convert the data sent over 
the yellow/violet wire pair back to RS-232 before connecting to surge protection. 
If you elect to use an alternate cable for power, you may also want to select an alternate 
cable for RS-485 communications. Some options include the Belden 3105A (Paired – 
EIA Industrial RS-485 PLTC/CM) or Alpha Wire 6010C 3PR 22 AWG. 
There are many reliable options available for wired power and communications 
connections (see Table 10). 
Communication 
Length (ft)  Cable 
Channel 1  Channel 2 
0 – 200 
SmartSensor cable  Native RS-485  Native RS-232 
200 – 1000 
SmartSensor cable  Native RS-485 
Click! conversion of 
RS-232 to RS-485 
1000 – 1400 
SmartSensor cable  Native RS-485  NA 
1000 – 2000 
Alternate power and communications 
cable 
Native RS-485 
Click! conversion of 
RS-232 to RS-485 
Table 10 – Cable Length Options 