User's Manual

CHAPTER 2 o CONNECTING POWER AND SURGE PROTECTION
22
Surge Protected Terminal Connections (Top)Figure 2.3 –
Figure 2.3 above shows the PROTECTED side of the Click! 200. The
UNPROTECTED side of the Click! 200 contains the same screw terminal
connections, but are reversed from left to right.
Note
See Appendix B for a description of how to wire the Click! 200 using the old
SmartSensor cable as well as for a cable connector pin out diagram.
Wiring to Earth Ground
ALL Click! 200 devices should be mounted on a DIN rail that is connected to
earth ground either through an earth-grounded chassis or a 16 AWG or larger
grounding wire aached to a 7-ft. (2.1-m) grounding rod. Follow the steps below
to correctly wire to earth ground:
Connect the grounding wire from either the DIN rail or a GND screw 1
terminal on the UNPROTECTED side of the Click! 200 to the lug bolt on the
inside of the pole-mount box.
Connect another grounding wire from the exterior lug bolt to earth ground 2
(see Figure 2.4).