Instructions / Assembly

Operation
NEVER run the pump
dry. Running pump
without water may cause seal damage.
Fill the pump with water before
starting.
PRIMING THE PUMP
After pump installation is complete, the
pump must be primed. Remove the pipe
plug in the discharge piping and fill the
pump and suction pipe with clean
water. Turn power to pump on. If the
pump does not pump water in 10
minutes, turn off the pump and refill
with clean water.
If the pump does not operate after
repeated attempts, check the following:
1. Vertical distance of pump to water
level must not be over 25 feet.
2. Suction piping must be air tight.
3. Be sure valve(s) are open if used in
discharge or suction piping.
NEVER run the pump
with a closed or
clogged discharge. The water inside the
pump could boil and damage the pump.
Maintenance
Maintain adequate ventilation for the
pump motor. The motor bearings are
permanently lubricated at the factory.
Additional lubrication is not required.
DRAINING FOR WINTER
Always protect pump and piping
against freezing temperatures. If there
is any danger of freezing, drain the
system. To drain the system:
1. Remove the pipe plug from the
discharge tee.
2. Remove the 1/4” plug from the
lower front face of the pump.
3. Drain all piping below the frost line.
3
Operating Instructions and Parts Manual
Electrical Connections
Connect the pump to a separate electrical
circuit with a dedicated circuit breaker.
Refer to the electrical specifications in
wiring chart for recommended fuse and
wire size.
Install and maintain wiring for this
pump in accordance with the National
Electrical code and all applicable local
electrical codes.
The motor must be grounded by
connecting a copper conductor to the
grounding screw provided within the
wiring compartment.
The voltage of power supply must match
the voltage of the pump. The WLS75,
WLS100 and WLS150 have dual voltage
motors preset at the factory to 230 volts.
The motors can be converted to 115 volts
by turning the voltage selector to the
desired voltage (See Figure 5). Use a
needle nose pliers to pull the selector out
approximately 1/4”, rotate and then
reinsert in correct position. NOTE: The
WLS200 cannot be converted; the
motor is 230 volts only.
CONNECTING WIRES
Terminal cover must be in place for safe
operation. Ground in accordance with local
and national electrical codes. Keep fingers
and objects away from openings and
rotating parts. Disconnect power sources
before touching internal parts. See Figure 6
for appropriate wiring locations.
www.waynepumps.com
WLS Series
Head
(ft)
Pressure (psi)
15 20 25 30
5 -- 5300 4800 4200
10 -- 5100 4500 3950
15 5300 4850 4250 3750
20 5150 4550 4000 3450
25 4850 4300 3750 3100
WLS200 - GPH
Head
(ft)
Pressure (psi)
15 20 25 30
5 4350 3950 3400 2950
10 4200 3700 3200 2750
15 3950 3450 3000 2500
20 3700 3250 2800 2150
25 3500 3050 2550 1700
WLS150 - GPH
Head
(ft)
Pressure (psi)
15 20 25 30
5 3650 3200 2800 2450
10 3450 3000 2650 2200
15 3250 2850 2450 1950
20 3050 2650 2300 1600
25 2850 2500 2050 1150
WLS100 - GPH
Head
(ft)
Pressure (psi)
15 20 25 30
5 3100 2700 2350 1950
10 2900 2550 2200 1700
15 2750 2400 2000 1400
20 2600 2200 1750 1000
25 2450 2050 1450 500
WLS75 - GPH
Figure 5 - Voltage Selector
Figure 6 - Connecting Wire
GROUND
SCREW
UNGROUNDED
LINE (L1)
TERMINAL
BOARD (L2)