Specifications
Operation / Installation Manual – FCF 5000, 9000, 12000, 16000, 24000 
Page 14 
Installation Checklist (Review Prior To Installation)   
Seawater cooling system:   
  Speed scoop located as far below the water line and as close to the keel as possible   
  Shut off valve (sea cock) and speed scoop properly sealed and tightened 
  Seawater pump is at least 1’ (305mm) below water line and securely mounted  
  Strainer mounted below pump with access to filter  
  Double/reversed stainless steel hose clamps on all hose connections   
  Thread sealer on all threaded connections   
  Hose runs uphill from speed scoop and sea cock to strainer, pump and air conditioning unit, then downhill (if 
possible) from air conditioner unit to overboard discharge   
  Water flowing freely from overboard discharge while pump is running  
  Pump relay panel, if used, must have its own circuit breaker sized for the pump (20 amp max)   
  All metal fittings should be bonded  
Mounting   
  Not in engine room or bilge area, must be sealed away from exhaust or fumes   
  Proper spacing allowed around unit   
  Attached to solid level platform with hold down brackets provided   
  Condensate drain routed aft and down hill to a sealed sump (not bilge) 
  All penetrations to bilge area sealed  
  Blower rotated toward supply air grille   
Electrical   
  All butt connections on pumps are tightly crimped and covered with heat shrink 
  AC power source installed and grounded/bonded in accordance with ABYC standards 
  Control wires connected to terminal strip with captive fork or ring terminals   
  Circuit breakers sized according to technical specifications section.   
  Pump Relay Panel (if used) has a dedicated circuit breaker sized for the pump but not to exceed 20 amps 
maximum.   
Grilles and Ducting   
  Supply air grille mounted as high as possible  
  Return air grille mounted as low and as close to the air conditioner as possible   
  Return air grille mounted away from bilge vapors or exhaust fumes   
  Ducting is pulled taut, straight, smooth and properly connected with no excess   
Quick Start Operations Checklist   
  Ensure seawater intake ball valve (sea cock) is open.  
  Turn on the air conditioners circuit breaker. If the seawater pump has its own circuit breaker, make sure to turn it 
on.   
  Turn the system on. Set the desired cabin temperature (set point). 
  Check for a steady solid stream of water from the overboard discharge.   
  Verify that there is steady airflow out of the supply air grille   
  If the unit does not appear to be operating properly, refer to troubleshooting guidelines. Note: Do not turn the 
unit off and immediately back on. Allow at least 30 seconds for refrigerant pressure equalization. 