Technical data

DBW 2010 / 2012 / 2020 / 2022 / 300 / 350  5.Error Search and Error Elimination 
505 
5.4.2  The heating device gives defect sign approximately 30 seconds after the heating device is 
started (at the control device 1563/6430 seconds (20 seconds at control device 1563/64). 
YES 
NO 
Is the thermal fuse F1 
disconnected? Is the heat 
classifier disconnected? Is the 
temperature classifier 
disconnected? 
The sound of the induction 
bobbin can be heard 
approximately after 20 or 12 
seconds. 
Is there voltage on the clamp
C8 and C5? (At the control
device 1563/64: Clamp D8 and
D5) 
Check the lines to the control 
device. Any break? 
Do you get the same result 
with a new induction bobbin? 
The induction bobbin is 
defective. Replace it. 
Eliminate the reason of 
disconnection. For instance, 
water is insufficient. Change the 
thermal fuse or set the 
temperature constrainer to zero. 
Fix the break. 
The isolator of the ignition 
electrodes is defective. 
Is the resistance / voltage of the flame regulator 100 kOhm when there 
is no light? (At the control device 1563/64: > 3.5 V) 
The flame regulator is 
defective. Replace it. 
the magnetic valve in the suction 
and return line open because the 
magnetic valve and tank are 
located high? 
The bobbin of the magnetic 
head is defective 
The control device is defective. 
Replace it. 
Do you hear a sound of 
combustion? 
Does fuel spray out of the
vaporizer nozzle? 
Yes 
Is there passage in the magnetic 
valves? 
The magnetic valve is defective. 
Replace it. 
Is there voltage in the 
magnetic valve? 
Control the incoming lines. 
No 
Does the setting of the ignition 
electrodes comply with the 
gauge? 
Adjust the ignition electrodes 
according to the gauge. 
Is fuel sent to the pump? 
Is there fuel in the tank? 
Fill fuel. 
The vaporizer nozzle is 
clogged. Replace it. 
Are all fuel lines connected? 
Tighten. New gasket. 
Is the gasket surface of the 
regulation piston or the air 
evacuation hole dirty? 
Dismantle the fuel pump. Is the 
dragging nail on the shaft 
okay? 
The suction line is clogged. It is 
either paraffin decomposition or 
the water in the fuel is frozen. 
Or the hole in the ventilation in 
the tank is clogged. 
Is the resistance / voltage of the 
flame regulator 1.56 kOhm with 
50 Lux light? (At the control 
device 1563/64: < 3.5 V) 
Does the nozzle spray with a 
limited angle? 
Check the conductivity of the 
suction and exhaust clamping 
sleeves and clean it. 
Replace it or clean it. 
No 
The flame regulator is defective. 
Replace it. 
The voltage control device in 
the heating device is at the 
border of the low voltage 
protection. 
No 
Recharge the battery. 
Is the viscosity under 20 c St? 
The vaporizer nozzle is 
clogged. Replace it.
Yes 
Yes 
The fuel quality does not comply 
with the mixture 
p
ro
p
ortion in the 
cold weather instruction. 
The sieve of the suction 
connection in the fuel pump is 
dirt. Clean it. 
Replace the fuel pump 