Datasheet
www.weg.net
Motor Protective Circuit Breakers22
Altitude
(above sea level) - h
Rated operational voltage
U
e
Current correction factor
I
u
h ≤ 2,000 m 690 V 1 x I
u
2,000 < h ≤ 3,000 m 550 V 0.96 x I
u
3,000 < h ≤ 4,000 m 480 V 0.93 x I
u
4,000 < h ≤ 5,000 m 420 V 0.90 x I
u
Motor Protective Circuit Breakers MPW - Technical Data
Altitude - Correction Factor
The MPW motor protective circuit breakers do not undergo
any change to their specified performance when applied at
an altitude of up to 2,000 meters above sea level.
However, as the altitude increases, the atmospheric
properties vary in terms of dielectric rigidness and pressure.
Therefore, current and voltage correction factors must be
applied for altitudes exceeding 2,000 meters, as shown in the
following table.
Reference code MPW16 MPW16i MPW12_S MPW12i_S
Maximum rated current i
max
(i
u
) 16 A 16 A 12 A 12 A
Number of poles 3 3 3 3
Instantaneous short-circuit 13 x I
e
max. 13 x I
e
max. 13 x I
e
max. 13 x I
e
max.
Rated operational voltage U
e
690 V
1)
690 V
1)
690 V
1)
690 V
1)
Rated operational frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Insulation voltage U
i
690 V 690 V 690 V 690 V
Rated impulse withstand voltage U
imp
6 kV 6 kV 6 kV 6 kV
Utilization category
IEC 60 947-2 (circuit breaker) A A A A
IEC 60 947-4-1 (motor starter) AC-3 AC-3 AC-3 AC-3
Tripping test Yes Yes Yes Yes
Overload protection Yes No Yes No
Phase failure sensitivity Yes No Yes No
Tripping indication Yes Yes Yes Yes
Tripping class 10 - 10 -
Maximum operation per hour Operations/hour 15 15 15 15
Altitude (m) 2,000 2,000 2,000 2,000
Degree of protection IP20 IP20 IP20 IP20
Mechanical life span Number of operations 100,000 100,000 100,000 100,000
Electrical life span Number of operations 100,000 100,000 100,000 100,000
Ambient temperatures allowed
Transport and storage -50...+80 °C -50...+80 °C -50...+80 °C -50...+80 °C
Operation
1)
-20...+70 °C -20...+70 °C -20...+70 °C -20...+70 °C
Temperature compensation -20...+60 °C - -20...+60 °C -
Resistance to impact (g) 15 15 15 15
Standards
IEC/EN 60 947-1. DIN VDE 0660 (part 100) Yes Yes Yes Yes
IEC/EN 60 947-2. DIN VDE 0660 (part 101) Yes Yes Yes Yes
IEC/EN 60 947-4-1. DIN VDE 0660 (part 102) Yes Yes Yes Yes
Terminal capacity
Type of terminal Flat Flat - -
Tightening torque
N.m 1.2...1.7 1.2...1.7 - -
lb.in 11...16 11...16 - -
Type of screws Philips (Nº2) Philips (Nº2) - -
Dimensions
Width (mm) 45 45 45 45
Height (mm) 90 90 100 100
Depth (mm) 77 77 77 77
Note: 1) Reduce current for temperatures exceeding +60 °C (87% to 70 °C).