User`s manual

16 | MW500
Installation and Connection
- English -
Table 3.1: Configuration of the switches to select the type of analog input and output signal on the CFW500-IOS
Input/
Output
Signal
Setting of
Switch S1
Signal
Range
Parameter Setting
AI1
Voltage S1.1 = OFF 0...10 V P0233 = 0 (direct reference) or 2 (inverse reference)
Current S1.1 = ON
0...20 mA P0233 = 0 (direct reference) or 2 (inverse reference)
4...20 mA P0233 = 1 (direct reference) or 3 (inverse reference)
AO1
Voltage S1.2 = ON 0...10 V P0253 = 0 (direct reference) or 3 (inverse reference)
Current S1.2 = OFF
0...20 mA P0253 = 1 (direct reference) or 4 (inverse reference)
4...20 mA P0253 = 2 (direct reference) or 5 (inverse reference)
NOTE!
Configuration to connect the RS485:
S1.3 = ON and S1.4 = ON: terminal RS485 ON.
S1.3 = OFF and S1.4 = OFF: terminal RS485 OFF.
Any other combination of the switches is not allowed.
For the correct connection of the control, use:
1) Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2) Maximum torque: 0.5 N.m (4.50 lbf.in).
3) Wiring of the plug-in module connector with shielded cables separated from the
other wiring (power, command in 110 V / 220 Vac, etc.), according to item 3.2.7 -
Cable Separation Distance. If those cables must cross other cables, it must be done
perpendicularly, keeping the minimum separation distance of 5 cm (1.97 in) at the
crossing point.
Connect the shield according to the figure below:
Do Not Ground
Insulate with Tape
Inverter
Side
Figure 3.5: Connection of the shield
4) Relays, contactors, solenoids or coils of electromechanical brakes installed close to
the drives may occasionally generate interference in the control circuitry. To eliminate
this effect, RC suppressors (with AC power supply) or freewheel diodes (with DC
power supply) must be connected in parallel to the coils of these devices.
5) When using the external HMIR (refer to section 7.2 - Accessories), the cable that
connects to the drive must be separated from the other cables in the installation,
keeping a minimum distance of 10 cm (3.94 in).
6) When using analog reference (AI1) and the frequency oscillates (problem of
electromagnetic interference), interconnect the GND of the connector of the plug-in
module to the drive grounding connection.