User`s manual

VVW Vector Control
10-4 | MW500
10
Power [P0404]
Frame
Voltage
[P0400]
(V)
Current
[P0401]
(A)
Frequency
[P0403]
(Hz)
Speed
[P0402]
(rpm)
Efficiency
[P0399]
(%)
Power
Factor
[P0407]
Stator Resistance
[P0409]
(Ω)
(HP) (kW)
0.16 0.12 63
230
0.73
50
1375 57. 0 0.72 30.62
0.25 0.18 63 1.05 1360 58.0 0.74 20.31
0.33 0.25 71 1.4 1310 59.0 0.76 14.32
0.50 0.37 71 1.97 1320 62.0 0.76 7. 27
0.75 0.55 80 2.48 1410 68.0 0.82 5.78
1.00 0.75 80 3.23 1395 72.0 0.81 4.28
1.50 1.10 90S 4.54 1420 7 7.0 0.79 2.58
2.00 1.50 90L 5.81 1410 79.0 0.82 1.69
3.00 2.20 100L 8.26 1410 81.5 0.82 0.98
4.00 3.00 100L 11.3 1400 82.6 0.81 0.58
5.00 3.70 112M 14.2 1440 85.0 0.83 0.43
7.5 0 5.50 132S 19.1 1450 86.0 0.84 0.25
10.0 7. 5 0 132M 25.7 1455 87.0 0.84 0.20
0.16 0.12 63
400
0.42
50
1375 57. 0 0.72 91.85
0.25 0.18 63 0.60 1360 58.0 0.74 60.94
0.33 0.25 71 0.80 1310 59.0 0.76 42.96
0.50 0.37 71 1.13 1320 62.0 0.76 21.81
0.75 0.55 80 1.42 1410 68.0 0.82 17.3 3
1.00 0.75 80 1.86 1395 72.0 0.81 12.85
1.50 1.10 90S 2.61 1420 7 7.0 0.79 7.73
2.00 1.50 90L 3.34 1410 79.0 0.82 5.06
3.00 2.20 100L 4.75 1410 81.5 0.82 2.95
4.00 3.00 100L 6.47 1400 82.6 0.81 1.75
5.00 3.70 112M 8.18 1440 85.0 0.83 1.29
7.5 0 5.50 132S 11.0 1450 86.0 0.84 0.76
10.0 7. 5 0 132M 14.8 1455 87. 0 0.84 0.61
15.0 11.0 160M 22.1 1455 88.5 0.81 0.35
20.0 15.0 160L 29.1 1460 89.7 0.83 0.24
P0178 – Rated Flux
Adjustable
Range:
0.0 to 150.0 % Factory
Setting:
100.0 %
Properties:
Access Groups
via HMI:
MOTOR
Description:
This parameter defines the desired flux in the motor air gap in percentage (%) of the rated flux. In general, it is not
necessary to modify the value of P0178 of the standard value of 100 %. However, some specific situations may
use values slightly above to increase the torque, or below to reduce the energy consumption.
NOTE!
Only in Scalar V/f Control, the parameter P0178 allows an output voltage regulation after V/f curve
defined. This is usefull for output voltage compensation or motor field weakening applications via
SoftPLC or Network control.
P0399 – Motor Rated Efficiency
Adjustable
Range:
50.0 to 99.9 % Factory
Setting:
75.0 %
Properties: cfg, VVW
Access Groups
via HMI:
MOTOR, STARTUP