Datasheet

Datenblatt
CP T SNT 90W 24V 3,8A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technische Daten
Erstellungs-Datum December 17, 2013 10:16:04 AM CET
Katalogstand xx.xx.xxxx / Technische Änderungen vorbehalten 2
Dimensions and weights
Width 35 mm
Height 110 mm
Depth 110 mm
Weight
0.5 kg
Net weight 516 g
Temperatures
Humidity 0...95 % (no condensation)
Operating temperature
-25 °C...+70 °C
Storage temperature -25 °C...+85 °C
Input
AC current consumption 1 A @ 230 V AC, 2.1 A @
115 V AC
AC input voltage range
85...264 V AC
Frequency range AC 47...63 Hz
Input fuse (internal) 4 A
Inrush current
< 20 A (230 V AC)
Recommended back-up fuse 6…16 A, char. B, circuit
breaker
Wire connection method
Screw connection
rated input voltage 100...240 V AC (wide-
range input)
output
Output voltage type DC
Output voltage, max. 28 V
Output voltage, min.
24 V
Output voltage, note (adjustable via
potentiometer on front)
Parallel connection option
yes, max. 5
Rated (nominal) output current @ U
Nom
3.8 A @ 40 °C
Wire connection method
Screw connection
continous output current @ 24 V DC 3.8 A @ 40 °C, 2.5 A @ 60
°C, 1.7 A @ 70 °C
rated output voltage
24 V DC ± 1 %
residual ripple, breaking spikes 100 mV
PP
@ 24 V DC, I
nenn
General data
AC failure bridging time @ I
Nom
min. 20 ms @ 230 V AC,
min. 10 ms @ 115 V AC
Current limiting
> 100 % I
N
Degree of efficiency typ. 85 % @ 230 V AC
Housing version Metal, corrosion resistant
Humidity
0...95 % (no condensation)
Indication Dual LED Operational:
green LED, Error: red LED
MTBF
> 1.8 mill. h
Mounting position, installation notice Horizontal on TS35 rail,
with 80 mm of clearance
at top and bottom for air
circulation; can be aligned
side-by-side with 50 mm
gap in between.
Operating temperature -25 °C...+70 °C
Weight 0.5 kg
EMC / shock / vibration
Limiting of mains voltage harmonic
currents
in accordance with EN
61000-3-2
Noise emission acc. to EN55022
Class B
Vibration resistance IEC 60068-2-6
3 axes, sinus, 10…55 Hz, 1
g, 1 oct/min.
Interference immunity test acc. to EN 61000-4-2 (ESD)|
EN 61000-4-3 and EN
61000-4-8 (fields)|EN
61000-4-4 (burst)|EN
61000-4-5 (surge)|EN
61000-4-6 (conducted)|
EN 61000-4-11 (dips)
Shock resistance IEC 60068-2-27 3 axes, half sinus, 15 g, 11
ms