User manual

Detaileddescriptionsoftheeld-buscoupler | EtherCAT eld-bus coupler UR20-FBC-EC
47Manual u-remote1432790000/03/02.2014
USB
PWR
SF
BF
MT
L/A IN
L/A OUT
RUN
ERROR
FBC-EC
Coupler power supply LED
green: supply voltage > 18V
red: at least one current path < 18V
3.1 Green: Input current path supply voltage >18VDC
3.2 Red: Input current path supply voltage <18VDC
3.4 Red: Internal fuse defective
4.1 Green: Output current path supply voltage >18VDC
4.2 Red: Output current path supply voltage <18VDC
4.4 Red: Internal fuse defective
LEDindicatorsUR20-FBC-EC,errormessages,seeChapter13
TD+ 1
TD– 2
RD+ 3
RD– 6
TD+ 1
TD– 2
RD+ 3
RD– 6
24 V DC for output
24 V DC for output
GND for output
GND for output
24 V DC for input
24 V DC for input
GND for input
GND for input
X1
X2
ConnectiondiagramUR20-FBC-EC
ATTENTION
Risk of material damage!
In the case of a maximum power supply of >8 A and a
maximum temperature of > +55 °C, all four contacts must
be connected with 1.5mm² wiring!