User manual
Detailed descriptions of I/O modules | Digital counter module UR20-2CNT-100
155Manual u-remote1432790000/03/02.2014
1-time counting
No primary counting direction
– 1-time counting from the load value
– Counting up or down
– Fixed setting of the count limit to the maximum counting
range
– If the upper or lower count limits are exceeded, the coun-
ter always jumps to the other count limit. Along with this
the status bits “Overflow performed” or “Underflow per-
formed” will be set and the internal gate will be closed
automatically. In addition, a process.
– Alarm can be triggered if it is parametrized
– To start the counting process once again, the internal
gate must be reopened
– In the event of interrupted gate control, the counting pro-
cess is continued at the respective current counter read-
ing.
– After a cancelled gate control, the counting process starts
with the load value
Countingrange
Limits Validrangeofvalues
Lower count limit –2 147 483 648 (–2
31
)
Upper count limit +2 147 483 647 (2
31
–1)
Upper
count limit
Lower
count limit
Load value
Gate start Gate startAutomatic
gate stop
Automatic
gate stop
Counter state
0
Overrun
Underrun
Time
1-timecounting,interruptedgatecontrol.
Upper
count limit
Lower
count limit
Load value
Gate start Gate startAutomatic
gate stop
Automatic
gate stop
Counter state
0
Overrun
Underrun
Time
1-timecounting,cancelledgatecontrol.
Primary counting direction up
– Up-counting starting at the load value
– If the end value -1 is reached during counting in the posi-
tive direction, the counter jumps to the load value at the
next positive count pulse and the internal gate is auto-
matically closed. In addition, a process alarm can be trig-
gered if it is parametrized.
– To restart the counting process, the internal gate must be
reopened and the counting starts at the load value
– It is possible to count beyond the lower count limit
Countingrange
Limits Validrangeofvalues
Lower count limit –2 147 483 647 (–2
31
+ 1) to +2 147 483 647 (2
31
–1)
Upper count limit +2 147 483 648 (–2
31
)
Lower
count limit
Load value
Gate start Gate startAutomatic
gate stop
Automatic
gate stop
Counter state
0
Overrun
End value
Underrun
Time
1-timecounting,primarycountingdirectionup.