User manual

Detailed descriptions of I/O modules | Digital counter module UR20-2CNT-100
155Manual u-remote1432790000/03/02.2014
1-time counting
No primary counting direction
1-time counting from the load value
Counting up or down
Fixed setting of the count limit to the maximum counting
range
If the upper or lower count limits are exceeded, the coun-
ter always jumps to the other count limit. Along with this
the status bits “Overflow performed” or “Underflow per-
formed” will be set and the internal gate will be closed
automatically. In addition, a process.
Alarm can be triggered if it is parametrized
To start the counting process once again, the internal
gate must be reopened
In the event of interrupted gate control, the counting pro-
cess is continued at the respective current counter read-
ing.
After a cancelled gate control, the counting process starts
with the load value
Countingrange
Limits Validrangeofvalues
Lower count limit –2 147 483 648 (–2
31
)
Upper count limit +2 147 483 647 (2
31 
–1)
Upper
count limit
Lower
count limit
Load value
Gate start Gate startAutomatic
gate stop
Automatic
gate stop
Counter state
0
Overrun
Underrun
Time
1-timecounting,interruptedgatecontrol.
Upper
count limit
Lower
count limit
Load value
Gate start Gate startAutomatic
gate stop
Automatic
gate stop
Counter state
0
Overrun
Underrun
Time
1-timecounting,cancelledgatecontrol.
Primary counting direction up
Up-counting starting at the load value
If the end value -1 is reached during counting in the posi-
tive direction, the counter jumps to the load value at the
next positive count pulse and the internal gate is auto-
matically closed. In addition, a process alarm can be trig-
gered if it is parametrized.
To restart the counting process, the internal gate must be
reopened and the counting starts at the load value
It is possible to count beyond the lower count limit
Countingrange
Limits Validrangeofvalues
Lower count limit –2 147 483 647 (–2
31
+ 1) to +2 147 483 647 (2
31
 –1)
Upper count limit +2 147 483 648 (–2
31
)
Lower
count limit
Load value
Gate start Gate startAutomatic
gate stop
Automatic
gate stop
Counter state
0
Overrun
End value
Underrun
Time
1-timecounting,primarycountingdirectionup.