User manual

Detailed descriptions of I/O modules | Analogue input module UR20-4AI-RTD-DIAG
201Manual u-remote1432790000/03/02.2014
Overview of the editable parameters UR20-4AI-RTD-DIAG
Channel Description Options(Value) Default value
Temperature unit Degree Celsius (0) / Degree Fahrenheit (1) / Kelvin (2) Degree Celsius
0 ... 3 Measurement range PT100 -200 ... 850 Degree Celsius (0) / PT200 -200 ... 850 Degree Celsius (1) /
PT500 -200 ... 850 Degree Celsius (2) / PT1000 -200 ... 850 Degree Celsius (3) /
NI100 -60 ... 250 Degree Celsius (4) / NI120 -80 ... 260 Degree Celsius (5) /
NI200 -60 ... 250 Degree Celsius (6) / NI500 -60 ... 250 Degree Celsius (7) /
NI1000 -60 ... 250 Degree (8) / Cu10 -100 ... 260 Degree Celsius (9) /
Resistance 40Ω (10) / Resistance 80Ω (11) / Resistance 150Ω (12) /
Resistance 300Ω (13) / Resistance 500Ω (14) / Resistance 1000Ω (15) /
Resistance 2000Ω (16) / Resistance 4000Ω (17) / disabled (18)
disabled
0 ... 3 Connection type 2-wire (0) / 3-wire (1) / 4-wire (2) 2-wire
0 ... 3 Conversion time 240 ms (0) / 130 ms (1) / 80 ms (2) / 55 ms (3) / 43 ms (4) / 36 ms (5) 80 ms
0 ... 3 Channel diagnostics disabled (0) / enabled (1) disabled
0 ... 3 Limit value monitoring disabled (0) / enabled (1) disabled
0 ... 3 High limit value -32768 ... 32767 0
0 ... 3 Low limit value -32768 ... 32767 0