User manual

Detaileddescriptionsoftheeld-buscoupler | PROFINET IRT eld-bus coupler UR20-FBC-PN-IRT
45Manual u-remote1432790000/03/02.2014
TechnicaldataUR20-FBC-PN-IRT(OrderNo.1334880000)
System data
Connection
2 x RJ-45
Field-bus protocol
PROFINET IRT
Processimage
Input data width max. 512 bytes
Output data width max. 512 bytes
Parameter data max. 4362 bytes
Diagnostic data max. 1408 bytes
Number of modules
max. 64 active
Configurationinterface
USB 2.0
Transfer rate
Field-bus Max. 100Mbps
u-remote system bus Max. 48 Mbps
Fast start-up
< 500ms with a maximum of 10 modules
Supply
Supplyvoltageforsystemandinputs
24VDC +20 % / -15 %
Supplyvoltageforoutputs
24VDC +20 % / -15 %
Max. feed-in current for input modules
10A
Max. feed-in current for output modules
10A
Currentconsumption(internal),typ.
116mA
Connection data
Type of connection
“PUSH IN”
Line connection cross-section
Single-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
Fine-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
General data, see Section 3.2
OverviewofeditableparametersUR20-FBC-PN-IRT
Parameter Optional values Default value
Process alarm disabled / enabled disabled
Diagnostic alarm disabled / enabled disabled
Type of diagnostic Extended channel diagnostic (short diagnostic)
Manufacturer-specic diagnostic (complete diagnostic)
Extended channel diagnostic (short diagnostic)
Behaviour of outputs on eld-bus errors All outputs off / Enable substitute value / Hold last value All outputs off
Module behaviour on hot swap Continue data exchange / Behaviour like eld-bus error Continue data exchange
Data format Motorola / Intel Motorola
Webserver via Ethernet disabled / enabled disabled