User manual
Detaileddescriptionsoftheeld-buscoupler | PROFINET IRT eld-bus coupler UR20-FBC-PN-IRT
45Manual u-remote1432790000/03/02.2014
TechnicaldataUR20-FBC-PN-IRT(OrderNo.1334880000)
System data
Connection
2 x RJ-45
Field-bus protocol
PROFINET IRT
Processimage
Input data width max. 512 bytes
Output data width max. 512 bytes
Parameter data max. 4362 bytes
Diagnostic data max. 1408 bytes
Number of modules
max. 64 active
Configurationinterface
USB 2.0
Transfer rate
Field-bus Max. 100Mbps
u-remote system bus Max. 48 Mbps
Fast start-up
< 500ms with a maximum of 10 modules
Supply
Supplyvoltageforsystemandinputs
24VDC +20 % / -15 %
Supplyvoltageforoutputs
24VDC +20 % / -15 %
Max. feed-in current for input modules
10A
Max. feed-in current for output modules
10A
Currentconsumption(internal),typ.
116mA
Connection data
Type of connection
“PUSH IN”
Line connection cross-section
Single-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
Fine-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
General data, see Section 3.2
OverviewofeditableparametersUR20-FBC-PN-IRT
Parameter Optional values Default value
Process alarm disabled / enabled disabled
Diagnostic alarm disabled / enabled disabled
Type of diagnostic Extended channel diagnostic (short diagnostic)
Manufacturer-specic diagnostic (complete diagnostic)
Extended channel diagnostic (short diagnostic)
Behaviour of outputs on eld-bus errors All outputs off / Enable substitute value / Hold last value All outputs off
Module behaviour on hot swap Continue data exchange / Behaviour like eld-bus error Continue data exchange
Data format Motorola / Intel Motorola
Webserver via Ethernet disabled / enabled disabled