User manual

Detailed descriptions of I/O modules | Power-feed module for input current path UR20-PF-I
214 1432790000/03/02.2014Manual u-remote
6.25 Power-feedmoduleforinputcurrentpathUR20-PF-I
Power-feedmoduleforinputcurrentpathUR20-PF-I(OrderNo.1334710000)
The u-remote station's main power supply is fed in via the
coupler. A power-feed module must be connected if the
current demand of the series of input modules is too large.
Power-feed modules serve to refresh the current paths and
isolate the power supply. The maximum feed-in current in
the input current path via the 4-pole connector is 10 A. De-
tails required to calculate current demand and power supply
seesection4.5.
Power-feed modules are passive modules without eld bus
communication, therefore they are not considered during
conguration.
A maximum of three passive modules (power-
feed module, potential distribution module,
empty slot module) may be installed in succes-
sion, however the next module to be installed
must be an active module!
PF-I
3
2
4
3
1
24 V DC
24 V DC
GND
GND
ConnectiondiagramUR20-PF-I
ATTENTION
Risk of material damage!
In the case of a maximum power supply of >8 A and a
maximum temperature of > +55 °C, all four contacts must
be connected with 1.5mm² wiring!