User manual

Detailed descriptions of I/O modules | Digital input module with time stamp UR20-2DI-P-TS
85Manual u-remote1432790000/03/02.2014
TechnicaldataUR20-2DI-P-TS(OrderNo.1460140000)
System data
Data
Process, parameter and diagnostic data depend on the coupler used,
see the table in Section 4.10.
Interface
u-remote system bus
System bus transfer rate
48 Mbps
Inputs
Number
2
Sensor type
Type1 and Type3 sensors as per IEC 61131-2
Input filter
Filter time adjustable up to 40ms
Lowinputvoltage
<5V
Highinputvoltage
>11V
Max. input current per channel
3mA
Sensor supply
yes
Sensor connection
2-wire, 3-wire, 3-wire + FE
Reverse polarity protection
yes
Modulediagnosis
yes
Individualchanneldiagnosis
no
Time stamp data width
16 bits
Time stamp resolution
1µs
Supply
Supplyvoltage
24V DC +20 %/-15 %
Currentconsumption(I
IN
inthepowersegmentofthefield-bus
coupler),typ.
8mA
Currentconsumption(I
IN
intherespectivepowersegment)
<10mA + sensor feed
General data
Weight
83 g
Foradditionalgeneraldata,seeSection3.4
OverviewoftheeditableparameterUR20-2DI-P-TS
Channel Description Options(Value) Default value
0 ... 1 Input delay
no (0) / 0,3 ms (1) (not at PROFIBUS-DP) / 3 ms (2) / 10 ms (3) / 20 ms (4) /
40 ms (5) (not at PROFIBUS-DP)
3ms
0 ... 1 TimeStamp at edge 0-1 disabled (0) / enabled (1) disabled
0 ... 1 TimeStamp at edge 1-0 disabled (0) / enabled (1) disabled