User manual

Detailed descriptions of I/O modules | Digital output module UR20-16DO-P-PLC-INT
119Manual u-remote1432790000/03/02.2014
6.12 DigitaloutputmoduleUR20-16DO-P-PLC-INT
DigitaloutputmoduleUR20-16DO-P-PLC-INT(OrderNo.1315270000)
The digital output module UR20-16DO-P-PLC-INT can con-
trol up to 16 actuators each with a maximum of 0.5 A. The
actuators are connected via a standard at ribbon cable
connector. A status LED is assigned to each channel in a
separate block. The module electronics supplies the outputs
with power through the at ribbon cable connector from the
separate 4-pole connectors.
For the PLC connection, the following applies: a maximum
current of 2A (with a max. of 1A per contact) can be taken
from the +24V connections or fed through the 0V connec-
tions. In the case of a total current greater than 2 A, the com-
mon ground wire must be connected to the separate 4-pin
plug-in connector.
16 x DO
Total current > 2 ATotal current < 2 A
16 x DO
4
2
1
3
4
16DO·P
0
1
2 3
4 5
6 7
8 9
10 11
12 13
14 15
4
2
1
3
4
16DO·P
0
1
2 3
4 5
6 7
8 9
10 11
12 13
14 15
24 V DC
24 V DC
GND
GND
2019
1
24 V DC
24 V DC
GND
GND
2019
1
++
ConnectiondiagramUR20-16DO-P-PLC-INT