User manual
Earthingandshielding | Shielding of cables
251Manual u-remote1432790000/03/02.2014
ATTENTION
Material damage!
If it is only possible to have a one-sided shield connection
for reasons specic to the circuit or equipment, the second
side of the cable shield can be routed to the local reference
potential via a capacitor (with short connections). To pre-
vent disruptive discharges when interference pulses occur,
a varistor or a resistor can also be wired in parallel to the
capacitor.
As an alternative, a doubled version (galvanically isolated)
can be used, whereby the inner shield is connected on one
side and the outside shield is connected on both sides.
Equipotentialbonding
If system components are positioned separately from each
other, potential differences may arise, provided that:
– Power is provided from different sources
– The earthing is implemented at different system parts,
despite the cable shields being connected at both sides
A voltage equalising cable must be used for equipotential
bonding.
WARNING
Possible danger to life!
The shield must not be used for equipotential
bonding!
The following features are essential for a voltage equalising
cable:
– In the case of cable shields on both ends, the impedance
of the equalising cable must be considerably smaller than
that of the shield connection (maximum 10 % of its
impedance)
– When the length of the equalising cable is less than
200m, its cross-section must be at least 16 mm
2
If the
cable is greater than 200m in length, a cross-section of
at least 25 mm
2
is necessary.
– Large-surface connection with the PE conductor or the
earthing and corrosion protection are requirements for
long-term safe operation
– They must be made of copper or galvanised steel
– In order to keep the enclosed area as small as possible,
the equalising cable and signal cable must be routed as
close to each other as possible
Inductancewiring
For inductive loads, it is recommended that protective cir-
cuits be placed directly on the load. The earth (PE/FE) must
be connected in a neutral-point conguration according to
regulations for switch cabinets.
ATTENTION
Material damage due to electrical discharge!
When disassembled, u-remote modules and couplers are at
risk of ESD. Therefore, avoid touching bus connections with
bare hands, as this can lead to damage due to electrostatic
discharges.