User manual

LED indicators and troubleshooting | I/O modules
290 1432790000/03/02.2014Manual u-remote
Module LED Status Recommended action
UR20-PF-O-2DI-SIL, UR20-PF-O-2DI-DELAY-SIL
Status LED
red
Red:
Channel error or error in the supply voltage
Channel error
Check that the module has been snapped into place
properly.
Check supply voltage
Check channel error
Overload at the OSSD output level Remove cross connection at OSSD
External feed-in recognised from field side Measure voltage at OSSD pin (4.3) vs. GND (4.4).
If a voltage is present, check the wiring!
Attention: safety hazard! Shut down the system and
prevent it from switching on again!
Internal error detected Perform a cold start.
If the error has not been xed, send the module to Weidmül-
ler for a technical examination.
Interruption in one of the two safety loops of a safety
circuit for at least 3 seconds.
Check safety circuit for interruptions if an interruption of
the safety channel is not part of the application.
Cross connection between the safety loops for at least
3 seconds.
Check safety circuit for cross connections.
1.1 Off: Safety circuit 1 interrupted
Yellow: Safety circuit 1 OK
Check safety circuit 1
2.1 Off: Safety circuit 2 interrupted
Yellow: Safety circuit 2 OK
Check safety circuit 2
4.3 Green: Feed-in voltage in valid range